Service Settings Menu, Maintenance Menu
SiUS371901E
101
Remote Controller
∗
1. (For FXTQ-TA, CXTQ-TA models)
The actual fan speed is converted into the fan tap to be displayed. Therefore, if the fan speed is changed by
controls or external factors, the airflow rate set with the remote controller may differ from the fan tap display.
∗
2. (For FXTQ-TA models)
0 rpm
is displayed even if the fan is rotating.
(For CXTQ-TA models)
- rpm
is displayed even if the fan is rotating.
∗
3. (For FXTQ-TA, CXTQ-TA models)
The ON/OFF status of the humidifier connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB is
not displayed. The ON/OFF status of the humidifier connected to the wiring adaptor is displayed.
∗
4. Only for CXTQ-TA
∗
5. Displays
99
when it is more than 100%.
∗
6. Display unit is by 100 CFM.
(ex. Displays
19
for 1850 CFM. Displays
18
for 1849 CFM.)
Forced Defrost
Forced defrost ON
Enables the forced defrost operation.
Forced defrost OFF
Disables the forced defrost operation.
Error Display
Display error ON
Displays the error on the screen.
Display error OFF
Displays neither errors nor warnings.
Display warning ON
Displays a warning on the screen if an error occurs.
Display warning OFF
No warning is displayed.
Swap Unit No.
Current Unit No.
A unit No. can be transferred to another.
Transfer Unit No.
Addressed Sensor
Value
Unit No.: 0 - 15
Select the unit number you want to check.
Code
00
:
01
:
02
:
03
:
04
:
05
:
06
:
07
:
08
:
09
:
30: (
∗
4)
31: (
∗
4)(
∗
5)
32: (
∗
4)(
∗
5)
33: (
∗
4)
34: (
∗
4)(
∗
5)
35: (
∗
4)(
∗
6)
Remote controller thermistor (°F)
Suction air thermistor (°F)
Heat exchanger liquid pipe thermistor (°F)
Heat exchanger gas pipe thermistor (°F)
Indoor unit address No.
Outdoor unit address No.
Branch Selector unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
Displays thermostat step 1 ON/OFF.
Thermostat step 1 OFF: 00
Thermostat step 1 ON: 01
Displays the heat demand that CXTQ-TA is currently sending to
the gas furnace (%).
Displays the fan demand that CXTQ-TA is currently sending to
the gas furnace (%).
Current status of heat pump ON/OFF for CXTQ-TA
HP OFF: 00
HP ON: 01
Current status of gas combustion heating
Displays current heat actual status (%).
Current airflow of the fan
Displays current airflow (CFM).
Data
The corresponding data will be displayed, based on the unit
number and Code selected.
Maintenance Menu
Item 2
Remarks
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...