SiUS371901E
Special Control
Functions and Control
126
7.2.2 Oil Return Control in Heating Operation
Starting conditions
Part name
Electric symbol
Oil return control
Compressor
M1C
+1 to +6 steps from frequency to frequency when oil return is IN
at a constant level
Inverter fan
M1F, M2F
Same as normal control
Electronic expansion valve (Heat
exchanger upper)
Y1E
Same as normal control
Electronic expansion valve (Heat
exchanger lower)
Y3E
Electronic expansion valve (Subcooling
heat exchanger)
Y2E
Same as normal control
Electric expansion valve (Subcooling
injection)
Y4E
Same as normal control
Electronic expansion valve (Refrigerant
cooling)
Y5E
Same as normal control
Electronic expansion valve (Receiver
gas purge)
Y7E
0 pulse
Solenoid valve (Oil separator oil return)
Y1S
ON
Solenoid valve (Hot gas bypass)
Y2S
OFF
Solenoid valve (Liquid pipe)
Y3S
ON
Four way valve (HP/LP gas pipe)
Y4S
Hold
Four way valve (Heat exchanger lower)
Y5S
Hold
Four way valve (Heat exchanger upper)
Y6S
Hold
Solenoid valve (Accumulator oil return)
Y7S
Same as normal control
Ending condition
A lapse of 8 minutes while the frequency is more than that of oil
return control.
Indoor unit actuator
Cooling
Heating
Fan
Thermostat ON unit
Remote controller setting
Remote controller setting
Non-operating unit
OFF
OFF
Thermostat OFF unit
Remote controller setting
Remote controller setting
Electronic expansion valve
Thermostat ON unit
Normal control
Normal control
Non-operating unit
224 pulse
224 pulse
Thermostat OFF unit
Forced thermostat ON
224 pulse
Branch Selector unit actuator
Normal simultaneous cooling/heating
Normal heating
Cooling
Heating
Electronic
expansion
valve (EVSC)
Y1E
Thermostat ON
0 pulse
Subcooling degree control
0 pulse
Non-operating
0 pulse
0 pulse
0 pulse
Thermostat OFF
0 pulse
0 pulse
0 pulse
Electronic
expansion
valve (EVH)
Y2E
Thermostat ON
0 pulse
6,000 pulse
6,000 pulse
Non-operating
0 pulse
6,000 pulse
6,000 pulse
Thermostat OFF
0 pulse
6,000 pulse
6,000 pulse
Electronic
expansion
valve (EVL)
Y3E
Thermostat ON
6,000 pulse
0 pulse
0 pulse
Non-operating
6,000 pulse
0 pulse
0 pulse
Thermostat OFF
6,000 pulse
0 pulse
0 pulse
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...