Field Settings for Outdoor Unit
SiUS371901E
197
Field Settings and Test Operation
2.5.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
∗
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
0
COOL/HEAT
selection
Several systems as 1 zone change over
COOL/HEAT:
INDIVIDUAL:
VRV
indoor unit or A-B-C
input set mode.
MASTER: System is the COOL/HEAT
master unit.
SLAVE: System is not a COOL/HEAT
master.
2
.
0
0
Individual
0
Unified master
1
Unified slave
2
2
Low noise/
demand address
Used to make address setting for low noise/
demand operation.
2
.
0
2
0
0
Address
31
3
1
5
Indoor fan forced
H
Used to force the fan of indoor unit to H tap.
2
.
0
5
Normal operation
0
Indoor fan H
1
6
Forced
thermostat
Used to force all indoor units to operate
forced thermostat ON.
2
.
0
6
Normal operation
0
Forced thermostat ON
1
8
Te setting
(Cooling
operation)
Used to make setting of targeted
evaporating temperature for cooling
operation.
2
.
0
8
Auto
(6-17°C) (42.8-62.6°F)
0
6°C (42.8°F)
2
7°C (44.6°F)
3
8°C (46.4°F)
4
9°C (48.2°F)
5
10°C (50.0°F)
6
11°C (51.8°F)
7
9
Tc setting
Used to make setting of targeted
condensing temperature for heating
operation.
2
.
0
9
Auto
(38-46°C)
(100.4-114.8°F)
0
41°C (105.8°F)
1
43°C (109.4°F)
3
46°C (114.8°F)
6
12
External low
noise setting/
demand setting
Used to receive external low noise or
demand signal.
2
.
1
2
Input LNO/DE :
NO
0
: YES
1
13
AIRNET address Used to set address of AIRNET
2
.
1
3
0
0
Address
63
6
3
16
Heat pump
lockout 1
Used for heat pump lockout
2
.
1
6
OFF
0
ON
1
18
High ESP setting
FAN
Fan high static pressure setting
2
.
1
8
OFF
0
ON
1
20
Additional
refrigerant
charge
Used to perform additional refrigerant
charging operation (compressor operation).
2
.
2
0
Refrigerant charging
OFF
0
ON
1
21
Refrigerant
recovery and
vacuuming
Used to set the system to refrigerant
recovery mode (without compressor run).
2
.
2
1
Refrigerant recovery
OFF
0
ON
1
22
Automatic night-
time low noise
operation
Automatic night-time low noise operation.
Time for the operation is subject to the start
and end time settings.
2
.
2
2
OFF
0
Level 1
1
Level 2
2
Level 3
3
25
External low
noise level
Low noise level when the external low noise
signal is input at option DTA104A61.
2
.
2
5
Level 1
1
Level 2
2
Level 3
3
26
Automatic night-
time low noise
operation start
Time to start automatic “night-time low
noise” operation. (“Night-time low noise”
level setting should also be made.)
2
.
2
6
About 8:00 PM
1
About 10:00 PM
2
About 12:00 AM
3
~
~
~
~
~
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...