SiUS371901E
Field Settings for Outdoor Unit
Field Settings and Test Operation
200
78
Heat pump
lockout
temperature
Heat pump is locked out when the outdoor
ambient temperature is smaller than the
heat pump lockout temperature.
2
.
7
8
–26.1°C (–15°F)
0
–23.3°C (–10°F)
1
–20.5°C (–5°F)
2
–17.7°C (0°F)
3
–15°C (5°F)
4
–12.2°C (10°F)
5
–9.4°C (15°F)
6
–6.6°C (20°F)
7
–3.8°C (25°F)
8
–1.1°C (30°F)
9
1.6°C (35°F)
1
0
4.4°C (40°F)
1
1
7.2°C (45°F)
1
2
10°C (50°F)
1
3
Forced heat pump lockout
1
4
79
Heat pump
lockout release
differential
Heat pump would be resumed when the
outdoor ambient temperature is recovered
by differential above the heat pump lockout
temperature.
2
.
7
9
2.8°C (5°F)
0
5.6°C (10°F)
1
8.3°C (15°F)
2
81
Cooling comfort
setting
Cooling comfort setting
2
.
8
1
Eco
0
Mild
1
Quick
2
Powerful
3
82
Heating comfort
setting
Heating comfort setting
2
.
8
2
Eco
0
Mild
1
Quick
2
Powerful
3
89
Intermittent fan
operation
Used for intermittent fan operation setting
2
.
8
9
OFF
0
30 minutes OFF, 1 minute
ON with medium fan speed
1
30 minutes OFF, 1 minute
ON with high fan speed
2
90
Indoor unit
without power
Multi-tenant function setting
2
.
9
0
Invalid
0
Valid
1
92
Te target
temperature
upper limit
Used to make setting of targeted
evaporating temperature upper limit for
cooling and heat recovery operation.
2
.
9
2
L
0
M
1
H
2
97
Auxiliary heater
maximum
allowable
temperature
Auxiliary heater is allowed to energize when
the ambient temperature is smaller than the
auxiliary heater maximum allowable
temperature.
2
.
9
7
–17.7°C (0°F)
0
–15°C (5°F)
1
–12.2°C (10°F)
2
–9.4°C (15°F)
3
–6.6°C (20°F)
4
–3.8°C (25°F)
5
–1.1°C (30°F)
6
1.6°C (35°F)
7
4.4°C (40°F)
8
7.2°C (45°F)
9
10°C (50°F)
1
0
12.7°C (55°F)
1
1
15.5°C (60°F)
1
2
18.3°C (65°F)
1
3
Auxiliary heater always not allowed
1
4
Auxiliary heater always allowed
1
5
98
Auxiliary heater
maximum
allowable
temperature
release
differential
Auxiliary heater is not allowed to energize
when the outdoor ambient temperature is
recovered by differential above the auxiliary
heater maximum allowable temperature.
2
.
9
8
2.8°C (5°F)
0
5.6°C (10°F)
1
8.3°C (15°F)
2
No.
∗
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...