Field Settings for Outdoor Unit
SiUS371901E
209
Field Settings and Test Operation
[2-38]: Emergency operation “Master”
To disable permanent compressor operation: in case of single module or “Master” unit of a multi outdoor
system, this setting allows:
Default value: 0. Compressor operation enabled.
Field setting:
Set 3: master module is disabled permanently.
[2-39]: Emergency operation “Slave 1”
To disable permanent compressor operation of “Slave 1” unit of a multi outdoor system:
Default value: 0. Compressor operation enabled.
Field setting:
Set 3: Slave 1 module is disabled permanently.
[2-40]: Emergency operation “Slave 2”
To disable permanent compressor operation of “Slave 2” unit of a multi outdoor system:
Default value: 0. Compressor operation enabled.
Field setting:
Set 3: Slave 2 module is disabled permanently.
Combination table setting 2-38, 2-39 and 2-40:
[2-42]: Outdoor fan noise countermeasure
Change fans rotational speed and reduce noise by the interference of air blow noise between outdoor
units.
Default value: 0
Field setting:
Mode A: 1
Mode B: 2
[2-45]: Low ambient cooling
Default value: 0.
This setting is not applicable to multi Branch Selector unit.
[2-47]: Te target temperature during heat recovery operation
Default value: 0.
Change [2-47] to 0, 2-7 in function of required operation method during heat recovery operation.
disable
Master/
individual
Slave 1
Slave 2
module
2-38-3
2-39-3
2-40-3
[2-45]
Description
0 (default)
No low ambient cooling available.
1
Low ambient cooling available.
Value
[2-47]
Te target
0 (default)
Auto (6-17°C) (42.8-62.6°F)
2
6°C (42.8°F)
3
7°C (44.6°F)
4
8°C (46.4°F)
5
9°C (48.2°F)
6
10°C (50.0°F)
7
11°C (51.8°F)
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...