Troubleshooting by Error Code
SiUS371901E
309
Service Diagnosis
3.41 Refrigerant Overcharged
Error Code
F6
Applicable
Models
All outdoor unit models
Method of Error
Detection
Detect overcharged refrigerant according to outdoor air temperature, heat exchanger deicer
temperature, and liquid pipe temperature during check operation.
Error Decision
Conditions
When the amount of refrigerant, which is calculated using outdoor air temperature, heat exchanger
deicer temperature, and liquid pipe temperature during check operation, exceeds the regular
charge amount by 30% or more
(If refrigerant is charged slightly over the regular charge amount,
F6
may be displayed on the
remote controller.)
Supposed
Causes
Refrigerant overcharged
Disconnection of outdoor air thermistor
Disconnection of heat exchanger deicer thermistor
Disconnection of liquid pipe temperature thermistor
Troubleshooting
Check for the conditions of
mounting of the temperature
sensors of the outdoor air
thermistor, the heat exchanger
thermistor, and liquid pipe
thermistor to the piping.
Disconnect the outdoor air
thermistor, the heat exchanger
thermistor, and liquid pipe
thermistor from the outdoor
unit main PCB, and then make
measurement of resistance
using a multimeter.
Normal?
Remedy refrigerant overcharging.
YES
NO
NO
Replace the abnormal thermistors,
and then operate the system.
Properly connect the thermistors,
and then operate the system.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
CHECK 11
Are the temperature
sensors properly
mounted?
CHECK 11
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...