SiUS371901E
Troubleshooting by Error Code
Service Diagnosis
334
Troubleshooting
Notes:
∗
1. Make measurement of voltage at the power supply terminal block (X1M).
∗
2. Make measurement of voltage at the L1, L2 and L3 terminals of diode module located on the
inverter PCB during the compressor is in operation.
Is supply
voltage imbalance
over approximately
12 V? (
∗
1)
Correct the open phase of
power supply.
Open phase?
Is the
imbalance of voltage
applied to the inverter over
approximately
12 V? (
∗
2)
Rectify the power supply
voltage imbalance.
Take countermeasures (listed
below).
YES
YES
NO
NO
NO
Take countermeasures.
Defective noise filter, magnetic
relay, or wiring
Turn OFF the power supply,
and then check and repair
wirings in the main circuit and
defective components.
(1) Loose contact and wiring
disconnection between the
power supply and the
inverter
(2) Adhesion, meltdown, or
loose contact of magnetic
relay
(3) Wiring disconnection in or
loose contact of noise filter
Replace the inverter PCB.
REYQ-XATJU: A3P
REYQ-XAYDU: A3P
REYQ-XAYCU: A4P
YES
Explanation to users
∗
Use the document “Notice of Inspection Results” attached to spare part.
Hand the “Notice of Inspection Results” to user to ask
him/her to rectify the imbalance.
Be sure to explain user that “power supply
voltage imbalance” will occur and Daikin
accepts no responsibility for the imbalance.
Use equipment capable of constantly
recording power supply voltages (e.g.
Memory HiCorder) to record power
supply voltages between phases (R-S,
S-T, and R-T) for a period of
consecutive 1 week.
Power supply voltage imbalance
Even though power supply voltage
remains balanced when making
measurement, it often becomes
imbalanced during night-time (from
6:00 PM to 10:00 PM).
Even though the power
supply voltage is normal, the
error recurs.
<If voltage can be monitored>
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...