Check
SiUS371901E
389
Service Diagnosis
4.10 Broken Wire Check of the Relay Wires
1. Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
On the system shown below, turn OFF the power supply to all equipment, short circuit between
the outdoor-outdoor unit terminal F1 and F2 in the "Outdoor Unit A" that is farthest from the
central remote controller, and then conduct continuity checks between the transmission wiring
terminal blocks F1 and F2 of the central remote controller using a multimeter. If there is
continuity between the said terminal blocks, the outdoor-outdoor unit transmission wiring has no
broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the outdoor-
outdoor unit terminal of the "Outdoor Unit A" short circuited, conduct continuity checks between
the transmission wiring terminal blocks F1 and F2 of the unified ON/OFF controller. If there is no
continuity as well, conduct continuity checks between the outdoor-outdoor unit terminal of the
"Outdoor Unit E", between the outdoor-outdoor unit terminal of the "Outdoor Unit D", between
the outdoor-outdoor unit terminal of the "Outdoor Unit C", … in the order described, thus
identifying the place with continuity.
If the place with continuity can be identified, there may be broken wires in places before the said
place with continuity.
2. Procedure for checking indoor-outdoor unit transmission wiring for broken wires (for checking
the indoor-outdoor unit transmission wiring of the "Outdoor Unit C" for broken wires)
Turn OFF the power supply to all equipment, short circuit between the indoor-outdoor unit
terminal F1 and F2 in the "Outdoor Unit C", and then conduct continuity checks between the
transmission wirings F1 and F2 of the "Indoor Unit a" that is farthest from the "Outdoor Unit C"
using a multimeter. If there is continuity between the said transmission wirings, the indoor-
outdoor unit transmission wiring has no broken wires in it.
If there is no continuity, the transmission wiring may have broken wires. With the indoor-outdoor
unit terminal of the "Outdoor Unit C" short circuited, identify the place with continuity in the
transmission wiring of the "Indoor Unit b", transmission wiring of the "Indoor Unit c", and
transmission wiring of the "Indoor Unit d" in the order described.
If the place with continuity can be identified, there may be broken wires in places before the said
place with continuity.
CHECK 15
1. Short circuit
between the
outdoor-outdoor
unit terminal
parts.
Outdoor-outdoor Unit
Transmission Wiring
2. Check the transmission
wiring for continuity.
If there is continuity, the
indoor-outdoor unit
transmission has no
broken wires in it.
Indoor-outdoor Unit
Transmission Wiring
2. Short circuit between
the indoor-outdoor unit
terminal parts.
1. Check the transmission
wiring for continuity.
If there is continuity, the
outdoor-outdoor unit
transmission has no broken
wires in it.
Unified ON/OFF controller
Central remote controller
Summary of Contents for REYQ-XA
Page 1: ...Service Manual SiUS371901E REYQ72 456XATJU REYQ72 456XAYDU REYQ72 432XAYCU Heat Recovery 60 Hz...
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 425: ...SiUS371901E Wiring Diagrams Appendix 412 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition...