Special Control
SiUS371901EB
151
Part 4 Functions and Control
7.2.2 Oil Return Operation in Heating Operation
Starting conditions
Part name
Electric symbol
Oil return operation
Compressor
M1C
+1 to +6 steps from frequency to frequency when oil return
is IN at a constant level
Inverter fan
M1F, M2F
Same as normal control
Electronic expansion valve
(Heat exchanger upper)
Y1E
Same as normal control
Electronic expansion valve
(Heat exchanger lower)
Y3E
Electronic expansion valve
(Subcooling heat exchanger)
Y2E
Same as normal control
Electric expansion valve
(Subcooling injection)
Y4E
Same as normal control
Electronic expansion valve
(Refrigerant cooling)
Y5E
Same as normal control
Electronic expansion valve
(Receiver gas purge)
Y7E
0 pulse
Solenoid valve (Oil separator oil return)
Y1S
ON
Solenoid valve (Hot gas bypass)
Y2S
OFF
Solenoid valve (Liquid pipe)
Y3S
ON
Four way valve (HP/LP gas pipe)
Y4S
Hold
Four way valve (Heat exchanger lower)
Y5S
Hold
Four way valve (Heat exchanger upper)
Y6S
Hold
Solenoid valve (Accumulator oil return)
Y7S
Same as normal control
Ending condition
A lapse of 8 minutes while the frequency is more than that
of oil return operation.
Indoor unit actuator
Cooling
Heating
Fan
Thermostat ON unit
Remote controller setting
Remote controller setting
Non-operating unit
OFF
OFF
Thermostat OFF unit
Remote controller setting
Remote controller setting
Electronic expansion valve
Thermostat ON unit
Normal control
Normal control
Non-operating unit
224 pulse
224 pulse
Thermostat OFF unit
Forced thermostat ON
224 pulse
Branch Selector unit actuator
Normal simultaneous cooling/heating
Normal heating
Cooling
Heating
Electronic
expansion valve
(EVSC)
Y1E
Thermostat ON
0 pulse
Subcooling degree
control
0 pulse
Non-operating
0 pulse
0 pulse
0 pulse
Thermostat OFF
0 pulse
0 pulse
0 pulse
Electronic
expansion valve
(EVH)
Y2E
Thermostat ON
0 pulse
6,000 pulse
6,000 pulse
Non-operating
0 pulse
6,000 pulse
6,000 pulse
Thermostat OFF
0 pulse
6,000 pulse
6,000 pulse
Electronic
expansion valve
(EVL)
Y3E
Thermostat ON
6,000 pulse
0 pulse
0 pulse
Non-operating
6,000 pulse
0 pulse
0 pulse
Thermostat OFF
6,000 pulse
0 pulse
0 pulse
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...