Outline of Control (Indoor Unit)
SiUS371901EB
185
Part 4 Functions and Control
Note(s)
9.16.3 Economizer
When indoor and outdoor air temperatures are reversed, the compressor is stopped to let in the
outdoor air to save energy.
This operation is called economizer operation, and the equipment to detect indoor and outdoor air
temperatures and open and close the damper to perform this operation is called an economizer.
The economizer detects indoor and outdoor air temperatures, informs the air conditioner that the
economizer operation is ready, and opens and closes the damper.
The indoor unit stops the outdoor unit when it receives a signal from the economizer and performs
air supply operation.
When the indoor air temperature is cooled down sufficiently by the economizer operation, and it is
no longer necessary (thermostat OFF), the indoor unit outputs a signal to the economizer to close
the damper.
&
Other conditions
Stop the thermostat ON signal (
∗
1)
to the economizer.
Transfer the thermostat ON signal (
∗
1) to
the economizer.
•
Cooling mode
•
When the thermostat is ON
Thermostat ON signal
&
Cooling mode
When the thermostat is ON
External output: ON (
2)
OR
Tcon
≤
Ts’ continues for 1
minute
Economizer set time (
3):
Free cooling only
&
Economizer set time (
3)
≠
Free cooling only
Thermostat ON continues for
the economizer set time (
3)
Air conditioner operation is
stopped.
The remote controller indicates
cooling operation.
The fan tap follows the remote
controller.
Air conditioner operation is
started.
The remote controller
indicates cooling operation.
The fan tap follows the
remote controller.
Normal operation
Other
conditions
Free cooling
Free cooling & Mech Cooling
Operation
Remote control ON
Remote control OFF
Stop indoor unit ON signal (
∗
4)
to the economizer.
Transfer indoor unit ON signal (
∗
4) to the
economizer.
Indoor unit ON signal
∗
1. Thermostat ON signal: A signal to turn ON the indoor unit thermostat and allow the
economizer to open the damper.
It turns ON the relay on the X2M-ECONOMIZER2 on the PCB.
∗
2. External input ON is an input signal to the X1M-ECONOMIZER1 terminal on the PCB.
∗
3. Refer to
Optional Kit Setting (UV lamp + Humi Economizer) (for FXTQ-TA
and CXTQ-TA models)
on page 213.
∗
4. Remote control ON signal: Contact output which shows the operating status of the indoor
unit.
This signal turns on the relay X2M-CONTROL ON/OFF on the PCB.
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...