Troubleshooting by Error Code
SiUS371901EB
285
Part 6 Service Diagnosis
J8 - 01
Defective heat exchanger liquid upper thermistor (R4T)
(Master)
Refer to the
J8
flowchart and make a diagnosis of the
relevant thermistor of the relevant unit based on the
Error code shown to the left.
J8 - 02
Defective heat exchanger liquid upper thermistor (R4T)
(Slave 1)
J8 - 03
Defective heat exchanger liquid upper thermistor (R4T)
(Slave 2)
J8 - 08
Defective heat exchanger liquid lower thermistor (R5T)
(Master)
J8 - 09
Defective heat exchanger liquid lower thermistor (R5T)
(Slave 1)
J8 - 10
Defective heat exchanger liquid lower thermistor (R5T)
(Slave 2)
J9 - 01
Defective subcooling heat exchanger gas pipe thermistor
(R6T) (Master)
Refer to the
J9
flowchart and make a diagnosis of the
relevant thermistor of the relevant unit based on the
Error code shown to the left.
J9 - 02
Defective subcooling heat exchanger gas pipe thermistor
(R6T) (Slave 1)
J9 - 03
Defective subcooling heat exchanger gas pipe thermistor
(R6T) (Slave 2)
J9 - 08
Error detection of subcooling heat exchanger gas pipe
thermistor (R6T) (Master)
J9 - 09
Error detection of subcooling heat exchanger gas pipe
thermistor (R6T) (Slave 1)
J9 - 10
Error detection of subcooling heat exchanger gas pipe
thermistor (R6T) (Slave 2)
J9 - 11
Receiver gas purge thermistor (R13T) (Master)
J9 - 12
Receiver gas purge thermistor (R13T) (Slave 1)
J9 - 13
Receiver gas purge thermistor (R13T) (Slave 2)
JA - 06
Defective high pressure sensor (S1NPH): Open (Master)
Refer to the
JA
flowchart and make a diagnosis of the
relevant sensor based on the Error code shown to the
left.
JA - 07
Defective high pressure sensor (S1NPH): Short (Master)
JA - 08
Defective high pressure sensor (S1NPH): Open (Slave 1)
JA - 09
Defective high pressure sensor (S1NPH): Short (Slave 1)
JA - 10
Defective high pressure sensor (S1NPH): Open (Slave 2)
JA - 11
Defective high pressure sensor (S1NPH): Short (Slave 2)
JC - 06
Defective low pressure sensor (S1NPL): Open (Master)
Refer to the
JC
flowchart and make a diagnosis of the
relevant sensor based on the Error code shown to the
left.
JC - 07
Defective low pressure sensor (S1NPL): Short (Master)
JC - 08
Defective low pressure sensor (S1NPL): Open (Slave 1)
JC - 09
Defective low pressure sensor (S1NPL): Short (Slave 1)
JC - 10
Defective low pressure sensor (S1NPL): Open (Slave 2)
JC - 11
Defective low pressure sensor (S1NPL): Short (Slave 2)
Error code
Troubleshooting
Error Description
Diagnosis
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...