Specifications
SiUS371901EB
25
Part 1 General Information
Model name (Combination unit)
REYQ192XATJU
REYQ192XATJA
Model name (Independent unit)
REYQ96XATJU
REYQ96XATJU
REYQ96XATJA
REYQ96XATJA
Power supply
3 phase, 208/230 V, 60 Hz
1 Cooling capacity
Nominal
Btu/h
(kW)
192,000 (56.3)
Rated
184,000 (53.9)
2 Heating capacity
Nominal
Btu/h
(kW)
216,000 (63.3)
Rated
206,000 (60.4)
Casing color
Ivory white (5Y7.5/1)
Dimensions: (H × W × D)
in (mm)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
Heat exchanger
Cross fin coil
Compressor
Type
Hermetically sealed scroll type
Volume
m
3
/h
17.7 + 17.7
Number of revolutions
r/min
5,214 + 5,214
Motor output × Number of units
kW
5.4 × 1 + 5.4 × 1
Starting method
Soft start
Fan
Type
Propeller fan
Motor output
kW
(0.8 × 2) × 2
Airflow rate
cfm
(m
3
/min)
7,989 + 7,989 (226 + 226)
Drive
Direct drive
Connecting
pipes
Liquid pipe
in (mm)
φ
5/8 (15.9) C1220T (Brazing connection)
Suction gas pipe
in (mm)
φ
1-1/8 (28.6) C1220T (Brazing connection)
High/Low pressure gas pipe
in (mm)
φ
1-1/8 (28.6) C1220T (Brazing connection)
Weight
lbs (kg)
727 + 727 (330 + 330)
Sound pressure level (Reference data)
dB (A)
64 (67.5
3)
Sound power level (Reference data)
dB
83
Safety devices
High pressure switch, Fan driver overload protector, Overcurrent fuse,
Inverter overload protector, Leak detecting device
Defrost method
Deicer
Capacity control
%
6-100
Refrigerant
Refrigerant name
R-410A
Charge
lbs (kg)
25.8 + 25.8 (11.7 + 11.7)
Control
Electronic expansion valve
Standard accessories
Installation manual, Operation manual, Connection pipes, Clamps
Drawing No.
Specification
3D120069B
Notes:
1
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB)/Outdoor temp.: 95°FDB (35.0°CDB)/Rated capacity is certified under AHRI standard 1230.
2
Indoor temp.: 70°FDB (21.1°CDB)/Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB)/Rated capacity is certified under AHRI standard 1230.
3
Sound pressure level may increase during heating operation at ambient temps below 41°F (5°C) value in parenthesis the max sound pressure at those conditions.
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...