SiUS371901EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
400
Note(s)
∗
NO
YES
YES
The
number of indoor
units connected to the
same system is not
more than 64.
Incorrect
electric heater
capacity setting
troubleshooting (
∗
1)
checked?
Replace the outdoor unit main
PCB (A1P).
Replace the outdoor unit main
PCB (A1P).
Refer to Incorrect electric heater
capacity setting troubleshooting.
(
∗
1)
Excess indoor units are
connected.
Check for the connection to
connect the proper number of
indoor units.
NO
Diagnosis Flowchart-1
UA-17
Error code
Sub code
NO
Is the
model of indoor unit
FXTQ-TA?
YES
NO
YES
Check
if the
refrigerant type of
the outdoor unit
corresponds to that
of the indoor
unit.
Replace the outdoor unit main
PCB (A1P).
Match the refrigerant types of the
outdoor unit and the indoor unit.
Diagnosis Flowchart-2
Error code
Sub code
UA-18
Summary of Contents for REYQ72-432XAYCU
Page 455: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 448 REYQ144 168XATJU REYQ144 168XATJA 2D119206B ...
Page 457: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 450 REYQ144 168XAYDU REYQ144 168XAYDA 2D119208C ...
Page 461: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 454 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 463: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 456 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 464: ...Wiring Diagrams SiUS371901EB 457 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C ...
Page 468: ...Wiring Diagrams SiUS371901EB 461 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 469: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 462 FXAQ07 09 12 18 24PVJU 3D075354F ...
Page 475: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 468 VAM1200GVJU 3D073270D ...
Page 478: ...Wiring Diagrams SiUS371901EB 471 Part 7 Appendix BS6 8Q54TVJ 2D089122B ...
Page 479: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 472 BS10 12Q54TVJ 2D089121B ...
Page 481: ...SiUS371901EB Wiring Diagrams Part 7 Appendix 474 BSF6 8Q54TVJ 2D123905A ...