Main/Sub Setting
SiUS371901E
91
Remote Controller
3.1.2 When an error occurred
U5: there are 2 main remote controllers when power is turned ON
Æ
Change the setting from Main to Sub on the remote controller you want to be Sub.
U8: there are 2 sub remote controller when power is turned ON
Æ
Change the setting from Sub to Main on the remote controller you want to be Main.
How to confirm Main/Sub setting
The Main/Sub setting of the remote controller is displayed on the bottom of the screen while
Checking the
connection. Please stand by.
is displayed.
How to change Main/Sub setting
You may change the Main/Sub setting of the remote controller while
Checking the connection. Please stand
by.
is displayed by pressing and holding the
Mode Selector
button for 4 seconds or longer.
1. It is not possible to change the Main/Sub setting from Main to Sub when only one remote
controller is connected.
2. When 2 remote controllers are being used, it is not possible to change the setting from Main to
Sub if one of the remote controllers is already set as Main.
3.2
When Wireless Remote Controller is Used Together
When using both a wired and a wireless remote controller for 1 indoor unit, the wired controller should be set to
Main. Therefore, the Main/Sub switch (SS1) of the signal receiver PCB must be set to Sub.
Checking the connection.
Please stand by.
Main RC
Confirm the remote controller
Main/Sub setting after power
is turned ON.
Checking the connection.
Please stand by.
Error Code: U5
Main RC
Press and hold for 4 seconds
or longer the Mode Selector
button of sub remote
controller side.
Checking the connection.
Please stand by.
Sub RC
Fan
Notes:
Main
/Sub
Main
Sub
Main
/Sub
switch (SS1)
S
M
S
M
Transmitter assembly
1
2 3
M
S
SS2
SS1
The side painted black indicates
the switch knob position.
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...