Address Setting for Wireless Remote Controller
SiUS371901E
93
Remote Controller
Setting for wireless remote controller
The address for the wireless remote controller is set to 1 at the factory. To change the setting, proceed as
follows:
1. Press
FILTER SIGN RESET
button and
INSPECTION/TEST
button at the same time for 4 seconds to enter
field setting mode. (
SETTING
is indicated on the display.)
2. Press
FAN
button and select
A
or
b
. Each time the button is pressed, the display switches between
A
and
b
.
3. Press
UP
button or
DOWN
button to select an address from 1-3 as same as the receiver.
Address can be set from 1-6, but the receiver does not work with addresses 4-6.
4. Press
RESERVE
button to confirm the setting.
5. Press
INSPECTION/TEST
button for 1 second to return to normal mode.
Multiple Settings A/b
The command such as operation mode or temperature setting by this remote controller will be rejected when the
target indoor unit operation is restricted as by an external control such as centralized control.
Since the setting acceptance is hard to discriminate with such circumstances there are two setting options
provided to enable discriminating by a beeping sound according to the operation: “A: Standard” or “b: Multi
System”. Set the setting according to the customer's intention.
Field setting mode
Address
Multiple setting
UP
button
DOWN
button
FAN
button
RESERVE
button
FILTER SIGN RESET
button
INSPECTION/TEST
button
Remote Controller
Indoor Unit
Multiple setting Display on remote
controller
Behavior to the remote controller operation when
the functions are restricted as by an external
control.
Other than the left
A:
Standard
(factory set)
All items displayed.
Accepts the functions except restricted. (Sounds
one long beep or three short beeps)
There may be a difference from the indoor unit
status with remote controller display.
Accepts all items transmitted
(Sounds two short beeps)
The remote controller
display agrees with the
indoor unit status.
b:
Multi
System
Display only items
transmitted for a
while.
<When some restricted functions are included
in the transmitted items>
Accepts the functions except restricted. (Sounds
one long beep or three short beeps)
There may be a difference from the indoor unit
status with remote controller display.
<When no restricted function is included>
Accepts all items transmitted (Sounds two short
beeps)
The remote controller display agrees with the
indoor unit status.
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...