SiUS371901E
Protection Control
Functions and Control
120
6.3
Discharge Pipe Protection Control
This discharge pipe protection control is used to protect the compressor internal temperature
against an error or transient increase of discharge pipe temperature.
Normal control
3-step down
9-step up
9-step down
3-step up
21-step down
After 30 seconds
After 20 seconds
After 20 seconds
After 30 seconds
A
(˚C) >
X
(˚C)
(
A
(˚F) >
Y
(˚F))
A
(˚C) <
X
–10
(˚C)
(
A
(˚F) <
Y
–18
(˚F))
A
(˚C) >
X
+5
(˚C)
(
A
(˚F) >
Y
+9
(˚F))
A
(˚C) <
X
–5
(˚C)
(
A
(˚F) <
Y
–9
(˚F))
A
(˚C) >
X
+10
(˚C)
(
A
(˚F) >
Y
+18
(˚F))
A
(˚C) >
X
+15
(˚C)
(
A
(˚F) >
Y
+27
(˚F))
A
(˚C) >
X
(˚C)
(
A
(˚F) >
Y
(˚F))
Compressor step: 1
After 20 seconds
HTdi > 135˚C (275˚F)
HTdi > 120˚C (248˚F)
continues for 10 minutes
Ti > 120˚C (248˚F)
continues for 5 seconds
Ti > 115˚C (239˚F)
continues for 10 minutes
OR
HTdi
: Value of compressor discharge pipe temperature (Tdi) compensated with outdoor air temperature
Ti
: Compressor body temperature
A
: Maximum of HTdi and Ti
X (˚C)(Y (˚F)) :
REYQ72-120XA
→
115˚C (239˚F) (constant)
REYQ144/168XA
→
Temperature determined by compressor rotation speed
Upper limit compressor step:
max (Max. Step)
Current
step
maintained
Discharge pipe temperature standby
(3 times within 100 minutes)
Abnormal stop
(
F3
is displayed)
Discharge pipe temperature
standby
(2 times within 100 minutes)
After 30
seconds
100
105
110
X (˚C)
212
221
230
80 90
120
Y (˚F)
Compressor
rotation speed (rps)
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...