Protection Control
SiUS371901E
121
Functions and Control
6.4
Compressor Body Protection Control
This compressor body protection control is used to protect the compressor internal temperature
against an error or transient increase of compressor body temperature.
Contents
The following control is performed for each compressor.
6.5
Inverter Protection Control
Inverter current protection control and radiation fin temperature control are performed to prevent
tripping due to an abnormality, or transient inverter overcurrent, and fin temperature increase.
In the case of multi-outdoor-unit system, each compressor performs these controls in the following
sequence.
Inverter overcurrent protection control
This control is performed for each compressor.
Normal control
Compressor body temperature standby
Reduce compressor capacity step
Compressor body
temperature > 108˚C
(226.4˚F)
Compressor body
temperature > 135˚C
(275˚F)
When occurring 3 times within 100
minutes, the error code
F3
is output.
(Sub code - 20, 21, 22)
Normal control
Inverter current standby
Reduce compressor capacity
A
B
When occurring 3 times within 60
minutes, the error code
L8
is
output.
C
Condition
REYQ72-
120XATJU
REYQ72-
120XAYDU
REYQ72-
120XAYCU
REYQ144/
168XATJU
REYQ144/
168XAYDU
REYQ144/
168XAYCU
A
more than 47.0 A more than 22.0 A more than 16.8 A more than 67.5 A more than 34.0 A more than 25.5 A
B
less than 45.6 A
less than 21.3 A
less than 16.3 A
less than 65.5 A
less than 33.0 A
less than 24.7 A
C
more than 50.0 A more than 25.0 A more than 17.3 A more than 72.0 A more than 38.0 A more than 26.0 A
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...