Outline of Control (Indoor Unit)
SiUS371901E
137
Functions and Control
∗
4. The control of auxiliary electric heater connected to FXTQ-TA models differ from this flowchart.
For details, refer to
Heater Control (FXTQ-TA Models)
∗
5. If the evaporator inlet temperature is kept at not more than –5°C (23°F) for a period of
cumulative 10 min. or not more than –1°C (30.2°F) for a cumulative period of 40 min., freeze-
up prevention operation will be conducted. If the evaporator inlet temperature is kept at not less
than 7°C (44.6°F) for a consecutive period of 10 min., the freeze-up prevention operation will
be reset.
∗
6. Thermostat status
∗
7. The following models have the drain pump as standard equipment.
FXFQ-T, FXZQ-TA, FXUQ-P, FXEQ-P, FXDQ-M, FXSQ-TA, FXMQ-PB
∗
8. Program dry display
No set temperature and airflow rate of the remote controller are displayed.
∗
9. Thermostat status
Set temperature when operating the program dry mechanism.
∗
10.Fan operation
By setting the remote controller to Fan, the fan will operate with thermostat OFF in set
temperature control operation mode.
∗
11.Set wind direction
According to wind direction instruction from the remote controller, the wind direction is set to
100% horizontal while in heating operation.
∗
12.Fan
According to fan speed instruction from the remote controller, the fan is put into operation in LL
mode while in heating operation.
∗
13.Wind direction
When the heating thermostat turns OFF, the wind direction will be set to 100% horizontal.
∗
14.Hot start
If the condenser inlet temperature exceeds 34°C (93.2°F) at the time of starting operation or
after the completion of defrost operation, or until 3 minutes pass or Tc is above 52°C (125.6°F),
hot starting will be conducted.
∗
15.Thermostat status
∗
16.Outlet air temperature drop protection
When the set temperature is below 24°C (75.2°F) or the electronic expansion valve opening is
small, the protection will be activated.
∗
17.
Hu
indicates the Humidifier connected to the wiring modification adaptor.
It is not related to the Humidifier terminals on the PCB of FXTQ-TA or CXTQ-TA.
∗
18.Only for CXTQ-TA.
Refer to
Gas
Furnace Control (CXTQ-TA Models)
OFF
ON
a
b
Set temperature
a = b = 1˚C (1.8˚F) or 0.5˚C (0.9˚F)
The values a and b depend on the field setting 12(22)-2.
Suction air temperature
b
a
–2˚C (28.4˚F)
–4˚C (24.8˚F)
Suction air temp.
Set temp.
b
a
(3)
(2)
(1)
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...