Outline of Control (Indoor Unit)
SiUS371901E
141
Functions and Control
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower near
the floor where the occupants are. When controlling by suction air thermistor only, the indoor unit
may therefore be turned off by the thermostat before the lower part of the room reaches the set
temperature. The temperature can be controlled so the lower part of the room where the occupants
are does not become cold by widening the range in which remote controller thermistor can be used
so that suction temperature is higher than the set temperature.
Assuming the set temperature in the figure above is 24°C (75°F), and the suction
temperature has changed from 18°C (64°F) to 28°C (82°F) (A
→
D):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat sensor is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 25°C (77°F) (A
→
C).
Remote controller thermistor is used for temperatures from 25°C (77°F) to 28°C (82°F) (C
→
D).
Assuming suction temperature has changed from 28°C (82°F) to 18°C (64°F) (D
→
A):
Remote controller thermistor is used for temperatures from 28°C (82°F) to 23°C (73°F) (D
→
B).
Suction air thermistor is used for temperatures from 23°C (73°F) to 18°C (64°F) (B
→
A).
Range in which remote controller
thermistor can be used
Range in which
suction air thermistor
can be used
Differential
Suction air temperature (TH1)
Set temperature (Ts)
12
14
16
18
20
22
24
26
28
30
32
34
53.6
57.2
60.8
64.4
68.0
71.6
75.2
78.8
82.4
86.0
89.6
93.2
°
C
°
F
°
C
32
30
28
26
24
22
20
18
16
°
F
89.6
86.0
82.4
78.8
75.2
71.6
68.0
64.4
60.8
TH1 = Ts + 12
≤
33
°
C
TH1 = Ts + 21.6
≤
91.4
°
F
TH1 = Ts + 10
≤
31
°
C
TH1 = Ts + 18
≤
87.8
°
F
TH1 = Ts + 1
≤
31
°
C
TH1 = Ts + 1.8
≤
87.8
°
F
TH1 = Ts – 1
°
C
TH1 = Ts – 1.8
°
F
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...