SiUS371901E
Outline of Control (Indoor Unit)
Functions and Control
144
9.4.3 Thermostat Control with Operation Mode Set to AUTO
The system will conduct this temperature control shown below, only when the wireless remote
controller or any central remote controller is connected.
Furthermore, setting changes of the differential value (
D
) can be made.
: Factory setting
Mode
No.
First code
No.
Contents of setting
Second code No.
01
02
03
04
05
06
07
08
12
(22)
4
Differential value while in AUTO
operation mode
0°C
0°F
1°C
1.8°F
2°C
3.6°F
3°C
5.4°F
4°C
7.2°F
5°C
9.0°F
6°C
10.8°F
7°C
12.6°F
Cooling thermostat ON
Cooling thermostat OFF
Heating thermostat ON
Heating thermostat OFF
(Ex.) When automatic cooling temperature is set to 27
°
C (80.6
°
F):
D
3
°
C (5.4
°
F)
2
D
(
+ 3.6)
°
F
2
D
(
+ 2)
°
C
Set cooling temperature
A
Set heating temperature
(
A
–
D
)
Display change
Cooling
→
Heating
Display change
Heating
→
Cooling
Differential value: 0
°
C (0
°
F)
30
°
C
(86
°
F)
Heating mode
Cooling mode
Control temp.
Differential value set to 1
°
C (1.8
°
F)
Set heating temp. Set cooling temp.
Heating mode
Control temp.
Differential value set to 2
°
C (3.6
°
F)
Heating mode
Control temp.
Differential value set to 3
°
C (5.4
°
F)
Heating mode
Cooling mode
Control temp.
Set heating temp. Set cooling temp.
Set heating temp. Set cooling temp.
Differential value set to 4
°
C (7.2
°
F)
Heating mode
Cooling mode
Control temp.
Differential value set to 5
°
C (9
°
F)
Set heating temp.
Set cooling temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 6
°
C (10.8
°
F)
Heating mode
Cooling mode
Control temp.
Differential value set to 7
°
C (12.6
°
F)
Heating mode
Cooling mode
Control temp.
Set cooling temp.
Set cooling temp.
Set heating temp.
Set cooling temp.
Set cooling/ heating temp.
25
°
C
(77
°
F)
27
°
C
(80.6
°
F)
26
°
C
(78.8
°
F)
24.5
°
C
(76.1
°
F)
27
°
C
(80.6
°
F)
29
°
C
(84.2
°
F)
24
°
C
(75.2
°
F)
25
°
C
(77
°
F)
27
°
C
(80.6
°
F)
28
°
C
(82.4
°
F)
23.5
°
C
(74.3
°
F)
24
°
C
(75.2
°
F)
27
°
C
(80.6
°
F)
20
°
C
(68
°
F)
21.5
°
C
(70.7
°
F)
23
°
C
(73.4
°
F)
27
°
C
(80.6
°
F)
21
°
C
(69.8
°
F)
22
°
C
(71.6
°
F)
24
°
C
(75.2
°
F)
27
°
C
(80.6
°
F)
22
°
C
(71.6
°
F)
22.5
°
C
(72.5
°
F)
25
°
C
(77
°
F)
27
°
C
(80.6
°
F)
23
°
C
(73.4
°
F)
26
°
C
(78.8
°
F)
27
°
C
(80.6
°
F)
Cooling
mode
Cooling
mode
Set heating
temp.
Set heating
temp.
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...