Outline of Control (Indoor Unit)
Functions and Control
160
9.16.3 Economizer
When indoor and outdoor air temperatures are reversed, the compressor is stopped to let in the
outdoor air to save energy.
This operation is called economizer operation, and the equipment to detect indoor and outdoor air
temperatures and open and close the damper to perform this operation is called an economizer.
The economizer detects indoor and outdoor air temperatures, informs the air conditioner that the
economizer operation is ready, and opens and closes the damper.
The indoor unit stops the outdoor unit when it receives a signal from the economizer and performs
air supply operation.
When the indoor air temperature is cooled down sufficiently by the economizer operation, and it is
no longer necessary (thermostat OFF), the indoor unit outputs a signal to the economizer to close
the damper.
Thermostat ON signal
Operation
Indoor unit ON signal
∗
1. Thermostat ON signal: A signal to turn ON the indoor unit thermostat and allow the economizer
to open the damper.
It turns ON the relay on the X2M-ECONOMIZER2 on the PCB.
∗
2. External input ON is an input signal to the X1M-ECONOMIZER1 terminal on the PCB.
∗
3. Refer to
Optional Kit Setting (UV lamp + Humi Economizer) (for FXTQ-TA and
CXTQ-TA models)
∗
4. Remote control ON signal: Contact output which shows the operating status of the indoor unit.
This signal turns on the relay X2M-CONTROL ON/OFF on the PCB.
&
Other conditions
Stop the thermostat ON signal (
∗
1)
to the economizer.
Transfer the thermostat ON signal (
∗
1) to
the economizer.
•
Cooling mode
•
When the thermostat is ON
&
•
Cooling mode
•
When the thermostat is ON
•
External output: ON (
∗
2)
OR
•
Tcon
≤
Ts’ continues for 1
minute
•
Economizer set time (
∗
3):
Free cooling only
&
•
Economizer set time (
∗
3)
≠
Free cooling only
•
Thermostat ON continues for
the economizer set time (
∗
3)
•
Air conditioner operation is
stopped.
•
The remote controller indicates
cooling operation.
•
The fan tap follows the remote
controller.
•
Air conditioner operation is
started.
•
The remote controller
indicates cooling operation.
•
The fan tap follows the
remote controller.
Normal operation
Other
conditions
Free cooling
Free cooling & Mech Cooling
Remote control ON
Remote control OFF
Stop indoor unit ON signal (
∗
4)
to the economizer.
Transfer indoor unit ON signal (
∗
4) to the
economizer.
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...