Field Settings for Indoor Unit
SiUS371901E
179
Field Settings and Test Operation
Airflow Setting when Cooling Thermostat is OFF
This is used to set airflow to "LL airflow" when cooling thermostat is OFF.
Setting of Airflow Rate
Make the following setting according to the ceiling height. The second code No. is set to
01
at the factory.
FXFQ07-24T, FXUQ18/24P
FXFQ30-48T, FXUQ30/36P
FXZQ-TA, FXEQ-P
FXHQ-M, FXAQ-P
Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material kit of air discharge
outlet has been installed.) The second code No. is factory set to
01
.
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
6
01
LL tap
02
Set fan speed
03
OFF
Mode No.
First Code
No.
Second
Code No.
Contents
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard
Lower than
2.7 m
(8-3/4 ft)
Lower than
3.0 m
(10 ft)
Lower than
3.5 m
(11-1/2 ft)
02
High Ceiling 1
Lower than
3.0 m
(10 ft)
Lower than
3.3 m
(10-3/4 ft)
Lower than
3.8 m
(12-1/2 ft)
03
Higher Ceiling 2
Lower than
3.5 m
(11-1/2 ft)
Lower than
3.5 m
(11-1/2 ft)
—
Mode No.
First Code
No.
Second
Code No.
Contents
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard
Lower than
3.2 m
(10-1/2 ft)
Lower than
3.6 m
(12 ft)
Lower than
4.2 m
(13-3/4 ft)
02
High Ceiling 1
Lower than
3.6 m
(12 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
4.2 m
(13-3/4 ft)
03
Higher Ceiling 2
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
—
Mode No.
First Code
No.
Second
Code No.
Contents
Ceiling height
13 (23)
0
01
Standard
Lower than 2.7 m (8-3/4 ft)
02
High Ceiling 1
Lower than 3.0 m (10 ft)
03
Higher Ceiling 2
Lower than 3.5 m (11-1/2 ft)
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
0
01
Standard
02
Slight increase
03
Normal increase
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
1
01
F: 4-direction airflow
02
T: 3-direction airflow
03
W: 2-direction airflow
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...