Field Settings for Indoor Unit
SiUS371901E
183
Field Settings and Test Operation
Display of Error Codes on the Remote Controller (For BRC1E73 only)
Error code (four digits) is displayed for limited products.
Select two-digit display if four-digit display is not preferred.
Key-lock Pattern Settings (For BRC1E73 only)
Setting of key-lock pattern for the remote controller
∗
When the Second code No. is set to
04
, no menu operation is allowed without key-lock by pressing and holding
the menu button. Set the Second code No
.
to other than
04
to cancel it.
Setting "Restricted / Permitted" of Airflow Block
(For units with the infrared presence/floor sensor only)
Due to possibility of dew condensation, the airflow block function cannot be enabled when closure material kit,
fresh air intake kit, natural / separately installed evaporation humidifier, or branch air duct is equipped.
This setting will prevent the airflow block is advertently set to ON.
Ensure that this setting is "Disable airflow block" when using together with options listed above.
Room Temperature Display (For BRC1E73 only)
A "Detailed display screen" can be selected as the display screen. This setting is used if you do not want to
display "Room temperature display" on the "Detailed display screen."
Thermistor Sensor for Auto Changeover and Setback Control by the Remote Controller (For BRC1E73 only)
Select a thermistor to utilize for the cool/heat mode automatic changeover and setback functions.
The sensed temperature will be displayed on the remote controller as the room temperature.
Mode No.
First Code No.
Second Code No.
Contents
1b
4
01
—
02
Two-digit display
03
—
04
Four-digit display
Mode No.
First Code No.
Second Code No.
Contents
1b
12
01
No operation allowed
(Cancel procedure is displayed.)
02
No operation allowed
(Cancel procedure is not displayed.)
03
No menu operation is allowed.
04
No menu operation is allowed any time.
Mode No.
First Code No.
Second Code No.
Contents
1b
14
01
Airflow block permitted
02
—
03
—
04
—
05
Airflow block restricted
Mode No.
First Code No.
Second Code No.
Contents
1c
0
01
Room temperature is not displayed.
02
Room temperature is displayed.
Mode No.
First Code No.
Second Code No.
Contents
1c
1
01
Utilize the return air thermistor
02
Utilize the remote controller thermistor
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...