Field Settings for Outdoor Unit
SiUS371901E
193
Field Settings and Test Operation
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
•
Changing and access the setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds), you can select the wanted
setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
•
To quit and return to the initial status, press the
MODE (BS1)
button.
•
Changing the value of the selected setting in mode 2:
- Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds) you can select the
wanted setting. It is done by pressing the
SET (BS2)
button.
- Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
- Now the
SET (BS2)
button is used to select the required value of the selected setting.
- When the required value is selected, you can define the change of value by pressing the
RETURN (BS3)
button once.
- Press the
RETURN (BS3)
button again to start operation according to the chosen value.
Example:
Checking the content of parameter [2-18] (to define the high static pressure setting of the outdoor unit’s fan).
[A-B]=C in this case defined as: A=2; B=10; C=the value we want to know/change
Make sure the segment indication is as during normal operation (default situation when shipped from factory).
•
Press the
MODE (BS1)
button for over 5 seconds; result segment display:
•
Press the
SET (BS2)
button 18 times; result segment display:
•
Press the
RETURN (BS3)
button once; the value which is returned (depending on the actual field situation), is
the status of the setting. In the case of [2-18], default value is "0", which means the function is not active.
Result: mode2 setting 18 is addressed and selected, return value is the current setting situation.
•
To change the value of the setting, press the
SET (BS2)
button until the required value appears on the
segment indication. When achieved, define the setting value by pressing the
RETURN (BS3)
button once. To
the chosen setting, confirm again by pressing the
RETURN (BS3)
button.
•
To leave the monitoring function, press the
MODE (BS1)
button two times, you will return to the default
situation when shipped from factory.
Operating the DIP switches
By operating the DIP switches it is possible to:
Result: mode 2 is accessed.
Result: mode 2 setting 18 is addressed.
What to do with DIP switch DS1
1
Cool/Heat selector (refer to the manual of the Cool/Heat selector switch)
OFF: not installed (factory setting)
2-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
What to do with DIP switch DS2
1-4
NOT USED
DO NOT CHANGE THE FACTORY SETTING
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...