Field Settings for Outdoor Unit
SiUS371901E
195
Field Settings and Test Operation
2.5
Monitoring Function and Field Settings
The operation of the outdoor unit can further be defined by changing some field settings. Next to making field
settings it is also possible to confirm the current operation parameters of the unit. The setting can also be
performed via the PC configuration software.
Below relevant Monitoring mode (mode 1) and Field setting mode (mode 2) settings are explained in detail.
Making settings is done via the master outdoor unit.
2.5.1 Mode 1
Mode 1 can be used to monitor the current situation of the outdoor unit. Some field setting contents can be
monitored as well.
Below the settings in mode 1 are explained.
[1-0]:
shows whether the unit you are checking is a master or slave 1 unit.
No indication: undefined situation
0: outdoor unit is master unit
1: outdoor unit is slave 1 unit
Master and slave 1 indications are relevant in multiple outdoor unit system configurations. The allocation
of which outdoor unit is master and slave 1 are decided by the unit’s logic.
The master unit must be used to input field settings in mode 2.
[1-1]:
shows the status of night-time low noise operation.
1: unit is currently operating under low noise restrictions
0: unit is currently not operating under low noise restrictions
Night-time low noise operation reduces the sound generated by the unit compared to nominal operating
conditions.
Night-time low noise operation can be set in mode 2. There are two methods to activate night-time low
noise operation of the outdoor unit system.
The first method is to enable an automatic night-time low noise operation by field setting. The unit will
operate at the selected low noise level during the selected time frames.
The second method is to enable night-time low noise operation based on an external input. For this
operation an optional accessory is required.
[1-2]:
shows the status of power consumption limitation operation.
1: unit is currently operating under power consumption limitation
0: unit is currently not operating under power consumption limitations
Power consumption limitation reduces the power consumption of the unit compared to nominal operating
conditions.
Power consumption limitation can be set in mode 2.
There are two methods to activate power consumption limitation of the outdoor unit system.
The first method is to enable a forced power consumption limitation by field setting. The unit will always
operate at the selected power consumption limitation.
The second method is to enable power consumption limitation based on an external input. For this
operation an optional accessory is required.
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...