SiUS371901E
Field Settings for Outdoor Unit
Field Settings and Test Operation
196
[1-5]:
shows the current Te target parameter position.
[1-6]:
shows the current Tc target parameter position.
[1-10]: shows the total number of connected indoor units.
It can be convenient to check if the total number of indoor units which are installed match the total
number of indoor units which are recognized by the system. In case there is a mismatch, It is advised to
check the communication wiring path between outdoor and indoor units (F1/F2 communication line).
[1-13]: shows the total number of connected outdoor units.
It can be convenient to check if the total number of outdoor units which are installed matches the total
number of outdoor units which are recognized by the system. In case there is a mismatch, It is advised to
check the communication wiring path between outdoor and outdoor units.
[1-17]: shows the latest error code.
[1-18]: shows the 2nd last error code.
[1-19]: shows the 3rd last error code.
When the latest error codes were reset by accident on an indoor unit user interface, they can be checked
again through this monitoring settings.
[1-40]: shows the current cooling comfort setting.
[1-41]: shows the current heating comfort setting.
[1-42]: shows the current high pressure sensor value (psi).
[1-43]: shows the current low pressure sensor value (psi).
[1-44]: shows the current compressor speed (Hz).
[1-45]: shows the current EEV (heat exchanger upper) opening (pulse divided by 10).
[1-46]: shows the current EEV (heat exchanger lower) opening (pulse divided by 10).
[1-47]: shows the current discharge thermistor value (°F).
[1-49]: shows the current compressor body thermistor value (°F).
[1-50]: shows the current outdoor air thermistor value (°F).
[1-51]: shows the current compressor suction thermistor value (°F).
[1-52]: shows the current subcooling gas thermistor value (°F).
[1-53]: shows the current heat exchanger gas (upper) thermistor value (°F).
[1-54]: shows the current heat exchanger gas (lower) thermistor value (°F).
[1-55]: shows the current deicer thermistor value (°F).
[1-56]: shows the compressor run time (hour divided by 100).
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...