Field Settings for Outdoor Unit
Field Settings and Test Operation
198
No.
∗
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
27
Automatic night-
time low noise
operation stop
Time to stop automatic “night-time low
noise” operation. (“Night-time low noise”
level setting should also be made.)
2
.
2
7
About 6:00 AM
1
About 7:00 AM
2
About 8:00 AM
3
28
Power transistor
check
Used to troubleshoot DC compressor.
Inverter waveforms are output without wire
connections to the compressor. It is useful to
determine whether the relevant trouble has
resulted from the compressor or inverter
PCB.
2
.
2
8
OFF
0
ON (10 Hz)
1
29
Capacity priority
setting
Cancel the low noise level control if capacity
is required while low noise operation or
night-time low noise operation is in progress.
2
.
2
9
OFF
0
ON
1
30
Demand 1
setting
Used to make a change to the targeted
power consumption level when the demand
1 control signal is inputted.
2
.
3
0
Level 1 (60%)
1
Level 2 (65%)
2
Level 3 (70%)
3
Level 4 (75%)
4
Level 5 (80%)
5
Level 6 (85%)
6
Level 7 (90%)
7
Level 8 (95%)
8
31
Demand 2
setting
Used to use a targeted power current level
when the demand 2 control signal is input.
2
.
3
1
Level 1 (40%)
1
Level 2 (50%)
2
Level 3 (55%)
3
32
Normal demand
setting
Used to set permanent demand 1 or 2
control without inputting any external signal.
2
.
3
2
OFF
0
Demand 1 (2-30)
1
Demand 2 (2-31)
2
34
Indoor fan tap
setting
Indoor fan speed is limited to L tap
depending on connection capacity and
outdoor air temperature (Ta).
∗
1.Indoor condition A: Temperature
difference Average of (indoor air
temperature – set temperature) is less
than 1.5°C (2.7°F).
∗
2.Indoor condition B: Temperature
difference Average of (indoor air
temperature – set temperature) is 3°C
(5.4°F) or more.
2
.
3
4
Indoor capacity
≥
130%
0
Indoor capacity
≥
130% in heating
1
Remote controller setting (Not limited)
2
Limited in cooling when
Ta < 29.5°C (85.1°F) and Indoor
condition is in condition A (
∗
1)
Returned when
Ta > 32.5°C (90.5°F) or Indoor
condition is in condition B (
∗
2)
3
Limited in cooling when
Ta < 23.5°C (74.3°F) and Indoor
condition is in condition A (
∗
1)
Returned when
Ta > 26.5°C (79.7°F) or Indoor
condition is in condition B (
∗
2)
4
Limited in cooling when
Ta < 19.3°C (66.7°F) and Indoor
condition is in condition A (
∗
1)
Returned when
Ta > 22.3°C (72.1°F) or Indoor
condition is in condition B (
∗
2)
5
Limited in cooling when
Ta < 29.5°C (85.1°F)
Returned when
Ta > 32.5°C (90.5°F)
6
Limited in cooling when
Ta < 23.5°C (74.3°F)
Returned when
Ta > 26.5°C (79.7°F)
7
Limited in cooling when
Ta < 19.3°C (66.7°F)
Returned when
Ta > 22.3°C (72.1°F)
8
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...