SiUS371901E
Field Settings for Outdoor Unit
Field Settings and Test Operation
208
[2-32]: Forced, all time, power consumption limitation operation (no external control adaptor is required to
perform power consumption limitation)
If the system always needs to run under power consumption limitation conditions, this setting activates
and defines the level power consumption limitation that will be applied continuously. The level is
according to the table.
Default value: 0 (OFF).
Change [2-32] to 0, 1 or 2 in function of required limitation.
[2-34]: Indoor unit fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air temperature for energy saving.
Default value: 0.
Notes:
∗
1. Indoor condition A: Temperature difference Average of (indoor air temperature – set temperature) is
less than 1.5°C (2.7°F).
∗
2. Indoor condition B: Temperature difference Average of (indoor air temperature – set temperature) is
3°C (5.4°F) or more.
[2-35]: Height difference setting
Default value: 1
In case the outdoor unit is installed in the lowest position (indoor units are installed on a higher position
than outdoor units) and the height difference between the highest indoor unit and the outdoor unit
exceeds 40 m (130 ft), the setting [2-35] should be changed to 0.
Value
[2-32]
Restriction reference
0 (default)
Function not active
1
Follows [2-30] setting
2
Follows [2-31] setting
Value
[2-34]
Indoor fan tap setting
0 (default)
Fan speed is limited to L tap when indoor units
capacity
≥
130%.
1
In heating mode, fan speed is limited to L tap
when indoor units capacity
≥
130%.
2
Fan speed follows the setting of remote controllers
(not limited by indoor units connection capacity).
3
Limited in cooling when Ta < 29.5°C (85.1°F)
and Indoor condition is in condition A (
∗
1)
Returned when Ta > 32.5°C (90.5°F)
or Indoor condition is in condition B (
∗
2)
4
Limited in cooling when Ta < 23.5°C (74.3°F)
and Indoor condition is in condition A (
∗
1)
Returned when Ta > 26.5°C (79.7°F)
or Indoor condition is in condition B (
∗
2)
5
Limited in cooling when Ta < 19.3°C (66.7°F)
and Indoor condition is in condition A (
∗
1)
Returned when Ta > 22.3°C (72.1°F)
or Indoor condition is in condition B (
∗
2)
6
Limited in cooling when Ta < 29.5°C (85.1°F)
Returned when Ta > 32.5°C (90.5°F)
7
Limited in cooling when Ta < 23.5°C (74.3°F)
Returned when Ta > 26.5°C (79.7°F)
8
Limited in cooling when Ta < 19.3°C (66.7°F)
Returned when Ta > 22.3°C (72.1°F)
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...