Symptom-based Troubleshooting
SiUS371901E
231
Service Diagnosis
1.2
With Gas Furnace
1.3
Gas Furnace Lockout Reset
Furnace lockout is characterized by a non-functioning furnace (circulator blower may be running continuously)
providing a diagnostic LED code located on the furnace board.
Lockout results when a furnace control detects abnormal conditions. If the furnace is in "lockout", the following
methods can be used to clear the error.
a. Turn the remote controller OFF to clear the error. If the error is not cleared, proceed to next step.
b. Heat pump lockout conditions are met.
c. Set the setting temperature to maximum, then turn the remote controller ON.
d. Turn the remote controller OFF.
e. Turn the remote controller ON after around 15 seconds from procedure d.
The procedures c, d, and e will not work during certain outdoor unit operations, i.e. defrost, startup, compressor
stop, service mode etc.
If the LED of the
ON/OFF
button is flashing when you turn the remote controller ON, you cannot clear the error
with the method above. In that case, the error must be cleared using the gas furnace. Refer to the gas furnace
operation manual for more details.
Symptom
Supposed Cause
1
The gas furnace does not start operation.
The gas furnace does not start operation while the compressor
is during operation or under stop-control, or right after defrost IN
or defrost OUT. Wait until the operation becomes stable.
2
Operation does not switch from heat pump to gas furnace in
spite of low room temperature. Operation does not switch
from gas furnace to heat pump even though the room
temperature is nearing the set temperature.
This function is performed only with outdoor units which support
automatic switching between gas furnace and heat pump
interlocking with room temperature.
Some models are enabled to support automatic switching
between gas furnace and heat pump interlocking with outdoor
air temperature by setting heat pump lockout on an outdoor unit
side. However, the compressor stops while gas furnace is
during operation.
3
AA-03
(Gas furnace abnormality) is indicated on the remote
controller while no error is indicated on the PCB of the gas
furnace.
In some cases of gas furnace abnormality, error indication on
the remote controller is retained even after the abnormality is
removed. Execute combustion heating operation once or reset
the power source.
4
The airflow rate indication on the remote controller is not
consistent with the actual airflow rate of the indoor unit.
The airflow rate of the indoor unit during gas furnace
combustion heating depends on the intensity of combustion.
Therefore, the airflow rate of the indoor unit does not reflect the
airflow setting of the remote controller.
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...