Troubleshooting by Error Code
Service Diagnosis
238
3.2
Error Codes (Sub Codes)
If an error code like the one shown below is displayed when the navigation remote controller (BRC1E series) is in
use, make a detailed diagnosis or a diagnosis of the relevant unit.
3.2.1 Indoor Unit
Error code
Troubleshooting
Error description
Diagnosis
A0 - 01
External protection device abnormality
Refer to page 252.
A6 - 01
Fan motor locked
A locked fan motor current has been detected.
Turn the fan by hand to check for the connection of connectors.
A6 - 10
Fan overcurrent error
A fan motor overcurrent has been detected.
Check for the connection of the connector between the fan motor
and the fan PCB. If the connection is normal, replace the fan
motor. If this still cannot solve the error, replace the fan PCB.
A6 - 11
Fan position detection error
An error in the detection of position of the fan motor. Check for the
connection of the connector between the fan motor and the fan
PCB. If the connection is normal, replace the fan motor. If this still
cannot solve the error, replace the fan PCB.
A6 - 20
Indoor fan motor status abnormality
Refer to page 264.
A6 - 21
Low indoor airflow
Refer to page 265.
A8 - 01
Power supply voltage error
Check for the input voltage of the fan motor.
A9 - 01
Electronic expansion valve error
There is an error in the electronic expansion valve coil or a
connector disconnected.
A9 - 02
Refrigerant leakage detection error
Refrigerant leaks even if the electronic expansion valve is closed.
Replace the electronic expansion valve.
AA - 03
Gas furnace abnormality
Refer to page 271.
AH - 03
Transmission error (between the self-cleaning
decoration panel and the indoor unit)
(when the self-cleaning decoration panel is
mounted)
Check for the connection of the harness connector between the
panel PCB and the indoor unit PCB.
AH - 04
Dust detection sensor error
(when the self-cleaning decoration panel is
mounted)
Check for the connections of the connector X12A on the panel
PCB and the connectors X18A and X19A on the sensor PCB.
AH - 05
Dust collection sign error
(when the self-cleaning decoration panel is
mounted)
Check for clogging with dust at the dust collection port as well as
in the brush unit, S-shaped pipe, and dust box. Furthermore,
check for any stains of the light receiving and emitting parts of the
infrared unit.
AH - 06
Air filter rotation error
(when the self-cleaning decoration panel is
mounted)
Check for anything getting in the way of rotating the filter (e.g. the
filter comes off or the drive gear is clogged with foreign matter).
AH - 07
Damper rotation error
(when the self-cleaning decoration panel is
mounted)
The damper does not rotate normally. Check for any foreign
matter around the damper and for the operation of the gear and
limit switch.
AH - 08
Filter self-cleaning operation error
(when the self-cleaning decoration panel is
mounted)
The unit has not yet completed the filter self-cleaning operation
even after the lapse of specified period of time. Check for any
external noise, etc.
AH - 09
Filter self-cleaning operation start disabled error
(when the self-cleaning decoration panel is
mounted)
The unit has been put into a state in which the filter self-cleaning
operation is disabled. Check the unit for the operating conditions.
AJ - 01
Capacity setting error
There is an error in the capacity setting of the indoor unit PCB.
AJ - 02
Electronic expansion valve setting error
There is a fault in the setting of the gear type electronic expansion
valve/direct acting type electronic expansion valve.
C1 - 01
Transmission abnormality between indoor unit
PCB and fan PCB
Check for the conditions of transmission between the indoor unit
PCB and the fan PCB.
C1 - 07
Blower motor communication error
Refer to page 276.
C1 - 08
Climate Talk Communication error
Refer to page 277.
C6 - 01
Defective combination of indoor unit PCB and
the fan PCB
A combination of indoor unit PCB and the fan PCB is defective.
Check whether the capacity setting adaptor is correct and the
type of the fan PCB is correct.
Blower motor HP mismatch
C6 - 02
Indoor blower does not have required
parameters to function
Refer to page 281.
U4 - 01
Indoor-outdoor transmission error
Refer to the
U4
flowchart.
UA - 13
Refrigerant type error
The type of refrigerant used for the indoor unit is different from
that used for the outdoor unit.
UA - 15
Not applicable for self-cleaning decoration
panel [when the self-cleaning decoration panel
is mounted]
An outdoor unit is not applicable for the self-cleaning decoration
panel is connected.
UA - 17
Incorrect electric heater capacity setting
Refer to page 365.
Summary of Contents for REYQ72-456XATJU
Page 415: ...SiUS371901E Wiring Diagrams Appendix 402 REYQ144 168XATJU 2D119206A ...
Page 416: ...Wiring Diagrams SiUS371901E 403 Appendix REYQ72 96 120XAYDU 2D119207B ...
Page 417: ...SiUS371901E Wiring Diagrams Appendix 404 REYQ144 168XAYDU 2D119208B ...
Page 418: ...Wiring Diagrams SiUS371901E 405 Appendix REYQ72 96 120 144 168XAYCU 2D119209A ...
Page 421: ...SiUS371901E Wiring Diagrams Appendix 408 FXZQ05 07 09 12 15 18TAVJU 3D110443A ...
Page 423: ...SiUS371901E Wiring Diagrams Appendix 410 FXEQ07 09 12 15 18 24PVJU 3D098557A ...
Page 426: ...Wiring Diagrams SiUS371901E 413 Appendix FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B ...
Page 428: ...Wiring Diagrams SiUS371901E 415 Appendix FXHQ12 24 36MVJU 3D048116C ...
Page 429: ...SiUS371901E Wiring Diagrams Appendix 416 FXAQ07 09 12 18 24PVJU C 3D075354D ...
Page 435: ...SiUS371901E Wiring Diagrams Appendix 422 VAM1200GVJU 3D073270D ...
Page 437: ...SiUS371901E Wiring Diagrams Appendix 424 1 4 2 Multi Branch Selector Unit BS4Q54TVJ 3D089123B ...
Page 438: ...Wiring Diagrams SiUS371901E 425 Appendix BS6 8Q54TVJ 2D089122B ...
Page 439: ...SiUS371901E Wiring Diagrams Appendix 426 BS10 12Q54TVJ 2D089121B ...
Page 440: ...Revision History Month Year Version Revised contents 04 2019 SiUS371901E First edition ...