Si39-406
Selection of Location
Installation Manual REYQ96MTJU
141
3. Selection of Location
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial
environment.
If installed as a household appliance it could cause electromagnetic
interference
.
The VRV OUTDOOR units should be installed in a location that meets the following requirements:
1. The foundation is strong enough to support the weight of the unit and the floor is flat to prevent
vibration and noise generation.
2. The space around the unit is adequate for servicing and the minimum space for air inlet and air
outlet is available.
(refer to figure 1 and choose one of both possibilities)
3. There is no danger of fire due to leakage of inflammable gas.
4. Ensure that water cannot cause any damage to the location in case it drips out the unit (e.g. in
case of a blocked drain pipe).
5. The piping length between the outdoor unit and the indoor unit may not exceed the allowable
piping length. (see “Example of connection”)
6. Select the location of the unit in such a way that neither the discharged air nor the sound
generated by the unit disturb anyone.
7. Make sure that the air inlet and outlet of the unit are not positioned towards the main wind
direction. Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to
block the wind.
CAUTION
1. An inverter air conditioner may cause electronic noise generated from AM broadcasting.
Examine where to install the main air conditioner and electric wires, keeping proper distances
away from stereo equipment, personal computers, etc.
If the electric wave of AM broadcasting is particularly weak, keep distances of 10ft. or more and
use conduit tubes for power and transmission lines.
≥
3/8
≥
3/8
≥
3/8
≥
3/4
≥
3/4
≥
7 7/8
≥
2
≥
2
≥
2
≥
7 7/8
≥
15 3/4
≥
15 3/4
≥
2
≥
3/8
B1
B1
≥
11 3/4
A
A
A
A
A
B2
B2
H1
H2
≥
3 7/8
≥
3 7/8
≥
11 3/4
B1
B2
<
If
installed as a single unit
>
(Pattern 1)
(Pattern 2)
(Pattern 3)
(Pattern 1)
(Pattern 2)
(Pattern 3)
<
When
installed in serial
>
1
1
2
2
1
3
1
1
1
1
(in.)
H1
≤
59
H1=59+X
H2
≤
19 5/8
H2=19 5/8 + Y
A
≥
19 5/8
A
≥
19 5/8+X/2
B1
≥
11 3/4
B2
≥
3 7/8
B1
≥
11 3/4+Y/2
B2
≥
3 7/8+Y/2
1. Front side
2. No limit to wall height
3. Suction side
≥
60
5
3
1
4
2
2
(in.)
≥
40
≥
40
≥
40
≥
60
≥
60
≥
60
1. indoor unit
2. Branch switch, overcurrent breaker
3. remote controller
4. cool/heat selector
5. personal computer or radio
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...