Unpacking and Placing the Unit
Si39-406
144
Installation Manual REYQ96MTJU
5. Unpacking and Placing the Unit
Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.
Secure the unit to its base using foundation bolts. (Use four commercially available M12-type
foundation bolts, nuts, and washers.)
The foundation bolts should be inserted 13/16".
Make sure the base under the unit extended more than 30 1/8" behind the unit.
The height of the base should be at least 5 7/8" from the floor.
The unit must be installed on a solid longitudinal foundation (steelbeam frame or concrete) as
indicated in figure 4.
DO NOT USE STANDS TO SUPPORT THE CORNERS
CAUTION
1. Prepare a water drainage channel around the foundation to condensate waste water from
around the unit.
2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities
first.
3. If the unit is to be installed on a frame, install the waterproofing board within a distance of 5 7/8"
under the unit in order to prevent infiltration of water coming from under the unit.
Model
A (in.)
B (in.)
Q96 type
48 13/16
43 3/8
13/16
”
28 7/16 - 29
3 1/8
3 1/8
30 1/8
A
B
1
2
3
(in.)
1. Foundation bolt point (
φ
9/16" dia. : 4 positions)
2. Depth of product
3. Shape of outdoor unit's support leg and foundation
bolt positions
1
1. Do not use stands to support the corners.
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...