Refrigerant Piping
Si39-406
148
Installation Manual REYQ96MTJU
Mount the REFNET joint so that it branches either horizontally or vertically.
Mount the REFNET header so that it branches horizontally.
4. Pipe connection
•
Only use the flare nuts included with the unit.
Using different flare nuts may cause the refrigerant to leak.
•
Be sure to perform a nitrogen blow when brazing.
(Brazing without performing nitrogen replacement or releasing nitrogen into the piping will
create large quantities of oxidized film on the inside of the pipes, adversely affecting valves
and compressors in the refrigerating system and preventing normal operation.)
•
Do not use a flux when brazing the refrigerant pipe joints.
Use phosphor copper brazing (BCup) which does not require flux.
(Using a chlorine flux may cause the pipes to corrode, and if it contains fluoride it may cause
the refrigerant lubricant to deteriorate, adversely affecting the refrigerant piping system.)
Note:
The pressure regulator for the nitrogen released when doing the brazing should be set to 2.9 psi
or less.
5. Protection against contamination when installing pipes
•
Take measures to prevent foreign materials like moisture and contamination from mixing
into the system.
•
Great caution is needed when passing copper tubes through walls.
A
1
A-arrow diagram
2
B
3
B-arrow diagram
1. (Horizontal connections)
2. (Up to ±30 or vertically.)
3. (Horizontal connections)
Place
Installation period
Protection method
Outdoor
More than a month
Pinch the pipe
Less than a month
Pinch of tape the pipe
Indoor
Regardless of the period
1
2
4
5
6
3
7
1. Refrigerant piping
2. Location to be brazed
3. Nitrogen
4. Taping
5. Manual valve
6. Regulator
7. Nitrogen
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...