Si39-406
Refrigerant Piping
Installation Manual REYQ96MTJU
157
How to fill a tank with a siphon attached.
Fill with the tank upright. (There is a siphon tube inside, so there is no need to turn the tank
upside-down.)
Other ways of filling the tank
Fill with the tank upside-down.
Determine the amount of refrigerant to be added by referring to the table, write it down on the
included “Added Refrigerant” plate and attach it to the rear side of the front cover.
Note: refer to the example of connection for the amount to be added.
After the vacuum drying is finished, charge the additional refrigerant in its liquid state through
the liquid shutoff valve service port.
Taking into account following instructions:
1. Check that gas and liquid shutoff valves are closed.
2. Charge the specified weight of refrigerant.
If the outdoor unit is not in operation and the total amount cannot be charged, follow the
procedures for additional refrigerant charge shown below.
Make sure to use installation tools you exclusively use on R410A installations to withstand the
pressure and to prevent foreign materials from mixing into the system.
Note:
Procedures for charging additional refrigerant.
One outdoor unit installed:
1
2
3
4
5
6
7
8
9
16
10
11
15
14
12
17
13
1. Pressure reducing valve
2. Nitrogen
3. Tank
4. Siphon system
5. Measuring instrument
6. Vacuum pump
7. Valve A
8. Valve B
9. Suction gas line
10. Liquid line
11. Discharge gas line
12. Shutoff valve service port
13. Charge hose
14. Indoor unit
15. BS unit
16. Outdoor unit
17. Dotted lines represent
onsite piping
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...