Installation
Si39-406
34
General Information
Important points
1. Where the lengths of piping involved are particularly long then the air tight test should be carried
out block by block.
Example:
1. Indoor side
2. Indoor side + vertical pipes
3. Indoor side + vertical pipes + outdoor side
3.2.6
Vacuum Drying
What is vacuum
drying?
Vacuum drying is:
"The use of a vacuum pump to vaporize (gasify) the moisture (liquid) inside the pipes and expel it
leaving the pipes completely dry inside."
At 1 atm (760 mmHg) the boiling point (evaporating temperature) of water is 212°F (100°C) but if a
vacuum is created inside the pipes using a vacuum pump then the boiling point is rapidly reduced
as the degree of the vacuum is increased. If the boiling point is reduced to a level below that of the
ambient temperature then the moisture in the pipes will evaporate.
1. Pressure reducing valve
2. Nitrogen
3. Tank
4. Siphon system
5. Measuring instrument
6. Vacuum pump
7. Valve A
8. Valve B
9. Suction gas line
10.Liquid side
11.Discharge gas line
12.Shutoff valve service port
13.Charge hose
14.Indoor unit
15.BS unit
16.Outdoor unit
17.Dotted lines represent onsite piping
1
2
3
4
5
6
7
8
9
16
10
11
15
14
12
17
13
<Example>
When outside temperature is 44.9°F (7.2°C)
As shown in the table on the right, the degree
of vacuum must be lowered below
–752mmHg.
Boiling point
of water
°F (°C)
Pressure
∗
mmHg
Pa
Torr
psi
104 (40)
–705
7333
55
–13.69
86 (30)
–724
4800
36
–14.0
80 (26.7)
–735
3333
25
–14.2
75.9 (24.4)
–738
3066
22
–14.28
71.9 (22.2)
–740
2666
20
–14.31
69.0 (20.6)
–742
2400
18
–14.35
64.0 (17.8)
–745
2000
15
–14.41
59.0 (15.0)
–747
1733
13
–14.45
53.0 (11.7)
–750
1333
10
–14.51
→
44.9 (7.2)
–752
1066
8
–14.55
32 (0)
–755
667
5
–14.61
Above figures (mmHg) are gauge pressure readings.
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...