Si39-406
Test Operation
General Information
95
4.4.2.6 Setting of Vacuuming Mode
In order to perform vacuuming operation at site, fully open the expansion valves of indoor and
outdoor units to turn on some solenoid valves.
[Operating procedure]
c
With
Setting Mode 2
while the unit stops, set (B) Refrigerant recovery / Vacuuming mode to
ON. The expansion valves of indoor and outdoor units fully open and some of solenoid valves
open.
(H2P blinks to indicate the test operation, and the remote controller displays "Test Operation"
and "In Centralized control", thus prohibiting operation.)
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
d
Use the vacuum pump to perform vacuuming operation.
e
Press Mode button “BS1” once and reset “Setting Mode 2”.
4.4.2.7
Check Operation
To prevent any trouble in the period of installation at site, the system is provided with a test
operation mode enabling check for incorrect wiring, stop valve left in closed, coming out (or
misplacing with suction pipe thermistor) of discharge pipe thermistor and judgment of piping length,
refrigerant overcharging, and learning for the minimum opening degree of motorized valve.
Unit stopping
Press the TEST button for 5 seconds.
10 sec to 10 minutes
LED display (H1P~H7P) (
8
:
ON
9
:
BLINKING
3
:
OFF)
3383333
3933338
Pressure equalizing
Step 1
20 sec to 2 minutes
10 minutes
3 minutes
5 minutes
3933383
Cooling start control
Step 2
3933388
3933888
3938333
Stability waiting operation
Step 3
Pump down residual operation
Step 7
5 minutes
Standby for restarting
Completion
Step 8
•
Stop valve close check
•
Wrong wiring check
•
Refrigerant over change check
•
Piping length check
3933833
3933838
3933883
Judgement function
Step4~6
CHECK OPERATION FUNCTION
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...