Si39-406
Appendix
General Information
125
7.10.3 Example 3:
Drain pipe trap shape defective
Situation
Indoor unit was fitted with a drain trap but a leak occurred during subsequent operation.
Source of
Problem and
Remedial Action
The trap was not properly shaped thus preventing it from functioning effectively as a trap and
resulting in drain leakage. The trap was reshaped and the fault disappeared.
Main Points
Duct types (18~48) require a drain trap.
Reason: There is resistance on the air inlet side caused by the heat exchanger and air filter and this
in turn creates negative pressure in relation to the atmospheric pressure on the discharge side. If
there is no drain trap then air will be drawn in from the drain pipe and the waste water splashed
around giving rise to the risk of water overflowing from the drain pan. To avoid this problem it is
therefore necessary to design a trap which takes account of the maximum negative pressure which
is likely to be created on the suction side.
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...