Si39-406
Installation
General Information
43
3.2.8
Drain Pipe Work (Indoor)
Operational steps
Drain Pipe
Gradient and
Support
a) The drain pipe must be fitted at a gradient of at least 1/100.
The drain pipe should be as short as possible and free from airlocks.
b) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that
a gradient of 1/100 is maintained. (PVC pipes should not be bent)
Spacing of supports for horizontal piping
c) The length of pipe laid horizontally should be kept to a minimum.
Drain Trap
Fit any indoor unit whose drain pipe connection is subjected to negative pressure, with a drain trap.
(FXMQ30~48M only)
a) Rig the drain trap as shown in the drawing bellow.
b) Provide one trap per unit. A single trap for converging units will prove ineffective.
c) Rig the trap to allow for future cleaning.
Insulate drain pipe
Install indoor unit
Connect drain pipe
Check for water
leaks
(V0999)
Class
Nominal diameter
Spacing
Rigid PVC pipe
1"~1 1/2" (25~40mm)
3.28~4.92 ft (1~1.5m)
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...