background image

12 Operation

Installation and operation manual

27

RKXYQ5T7Y1B
VRV IV compressor unit for indoor installation
4P408443-1 – 2015.07

To adjust

For programming temperature, fan speed and air flow direction refer
to the operation manual of the user interface.

12.3

Using the dry program

12.3.1

About the dry program

▪ The  function  of  this  program  is  to  decrease  the  humidity  in  your

room with minimal temperature decrease (minimal room cooling).

▪ The  micro  computer  automatically  determines  temperature  and

fan speed (cannot be set by the user interface).

▪ The system does not go into operation if the room temperature is

low (<20°C).

12.3.2

To use the dry program (WITHOUT cool/
heat changeover remote control switch)

To start

1

Press the operation mode selector button on the user interface
several times and select 

 (program dry operation).

2

Press the ON/OFF button of the user interface.

Result: 

The  operation  lamp  lights  up  and  the  system  starts

operating.

3

Press  the  air  flow  direction  adjust  button  (only  for  double-flow,
multi-flow,  corner,  ceiling-suspended  and  wall-mounted).  Refer
to 

"12.4 Adjusting the air flow direction" on page 27

 for details.

To stop

4

Press the ON/OFF button on the user interface once again.

Result: 

The  operation  lamp  goes  out  and  the  system  stops

operating.

NOTICE

Do not turn off power immediately after the unit stops, but
wait for at least 5 minutes.

12.3.3

To use the dry program (WITH cool/heat
changeover remote control switch)

To start

1

Select  cooling  operation  mode  with  the  cool/heat  changeover
remote control switch.

1

1

2

Press the operation mode selector button on the user interface
several times and select 

 (program dry operation).

3

Press the ON/OFF button of the user interface.

Result: 

The  operation  lamp  lights  up  and  the  system  starts

operating.

4

Press  the  air  flow  direction  adjust  button  (only  for  double-flow,
multi-flow,  corner,  ceiling-suspended  and  wall-mounted).  Refer
to 

"12.4 Adjusting the air flow direction" on page 27

 for details.

To stop

5

Press the ON/OFF button on the user interface once again.

Result: 

The  operation  lamp  goes  out  and  the  system  stops

operating.

NOTICE

Do not turn off power immediately after the unit stops, but
wait for at least 5 minutes.

12.4

Adjusting the air flow direction

Refer to the operation manual of the user interface.

12.4.1

About the air flow flap

Double flow+multi-flow units

Corner units

Ceiling suspended units

Wall-mounted units

For  the  following  conditions,  a  micro  computer  controls  the  air  flow
direction which may be different from the display.

Cooling

Heating

▪ When the room temperature is

lower 

than 

the 

set

temperature.

▪ When starting operation.

▪ When the room temperature is

higher 

than 

the 

set

temperature.

▪ At defrost operation.

▪ When operating continuously at horizontal air flow direction.

▪ When continuous operation with downward air flow is performed

at the time of cooling with a ceiling-suspended or a wall-mounted
unit, the micro computer may control the flow direction, and then
the user interface indication will also change.

The air flow direction can be adjusted in one of the following ways:

▪ The air flow flap itself adjusts its position.

▪ The air flow direction can be fixed by the user.

▪ Automatic 

 and desired position  .

WARNING

Never touch the air outlet or the horizontal blades while the
swing  flap  is  in  operation.  Fingers  may  become  caught  or
the unit may break down.

NOTICE

▪ The  movable  limit  of  the  flap  is  changeable.  Contact

your dealer for details. (only for double-flow, multi-flow,
corner, ceiling-suspended and wall-mounted).

▪ Avoid operating in the horizontal direction 

. It may

cause dew or dust to settle on the ceiling or flap.

12.5

Setting the master user interface

12.5.1

About setting the master user interface

d

d

c

c

a

b

VRV DX

VRV DX

VRV DX

EKEXV

AHU

d

d

1

2

1

In case of VRV DX indoor units

Summary of Contents for RKXYQ5T7Y1B

Page 1: ...Installation and operation manual VRV IV compressor unit for indoor installation English Installation and operation manual VRV IV compressor unit for indoor installation RKXYQ5T7Y1B...

Page 2: ...e dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti at...

Page 3: ...components 15 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 and default situation 16 6 1 6 To use mode 2 17 6 1 7 Mode 1 and default situation Monitoring settings 17 6 1 8 Mode 2 Field settings...

Page 4: ...unit Heat exchanger unit installation manual Installation instructions Format Paper in the accessory bag of the heat exchanger unit Installer and user reference guide Preparation of the installation...

Page 5: ...stallation site 4 1 1 Installation site requirements of the compressor unit Service space Mind the following requirements 10 a 10 10 500 10 mm 3D098835 1 b a Top view b Front view NOTICE This is a cla...

Page 6: ...HP Piping outer diameter size mm Gas pipe Liquid pipe Standard Size up 5 15 9 19 1 9 5 C Piping between refrigerant branch kits Use the following diameters Indoor unit capacity index Piping outer diam...

Page 7: ...tted to the building use a vibration proof rubber field supply You can install the compressor unit directly on the floor or on a structure On the floor You do NOT have to fix the unit with anchor bolt...

Page 8: ...mm 22 5 27 5 5 3 2 To remove the pinched pipes WARNING Any gas or oil remaining inside the stop valve may blow off the pinched piping Failure to observe the instructions in procedure below properly ma...

Page 9: ...hole b Hit on the knockout hole and remove it c Remove the burrs d Paint the edges and areas around the edges using repair paint to prevent rusting NOTICE Precautions when making knockout holes Avoid...

Page 10: ...ping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been factory tested for leaks On...

Page 11: ...orrosive effect between the brass flare nut and the copper flare 5 4 5 To perform vacuum drying To remove all moisture from the system proceed as follows 1 Evacuate the system for at least 2 hours to...

Page 12: ...ill take longer then Stage 2 Manual charging Only necessary if the determined additional refrigerant amount is not reached yet by pre charging Stage 1 Pre charging Summary Pre charging Refrigerant bot...

Page 13: ...efrigerant on page 13 and solve the malfunction accordingly Resetting the malfunction can be done by pushing BS3 You can restart the Charging instructions Aborting the manual refrigerant charge is pos...

Page 14: ...cal wiring on the compressor unit NOTICE Follow the wiring diagram delivered with the unit located on the switch box cover Make sure the electrical wiring does NOT obstruct proper reattachment of the...

Page 15: ...C configurator You can also make field settings through a personal computer interface for this option EKPCCAB is required The installer can prepare the configuration off site on PC and afterwards uplo...

Page 16: ...re operation in order to have power running to the crankcase heater and to protect the compressor Turn on the power supply of the compressor unit heat exchanger unit and all indoor units When the comm...

Page 17: ...set in mode 2 There are two methods to activate low noise operation of the compressor unit and heat exchanger unit The first method is to enable an automatic low noise operation during night time by f...

Page 18: ...settings In mode 2 you can make field settings to configure the system The LEDs give a binary representation of the setting value number Setting binary Value Description 2 8 Te target temperature dur...

Page 19: ...ne the level of operation Depending on the chosen level the noise level will be lowered The start and stop moments for this function are defined under setting 2 26 and 2 27 default Deactivated Level 1...

Page 20: ...t exchanger unit while performing a test operation is dangerous NOTICE Be sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the c...

Page 21: ...erform a test run 7 3 1 About test run The procedure below describes the test operation of the complete system This operation checks and judges following items Check of wrong wiring communication chec...

Page 22: ...splayed on the user interface of the indoor unit 8 1 1 Error codes Overview Main code Cause Solution Heat exchanger fan malfunction Drain pump feedback contact is open In the heat exchanger unit Check...

Page 23: ...anger unit capacity setting malfunction Check the type of heat exchanger unit If necessary replace the heat exchanger unit Insufficient supply voltage Check if the supply voltage is supplied properly...

Page 24: ...vice port refrigerant charge f Filter 5 g Subcool heat exchanger h Pressure regulating valve i Capillary tube j Accumulator k Compressor accumulator l Heat exchanger M1C Compressor M1F M2F Fan motor R...

Page 25: ...g cooling applications NOTICE Do not use the air conditioner for other purposes In order to avoid any quality deterioration do not use the unit for cooling precision instruments food plants animals or...

Page 26: ...om dropping or cold air from blowing Defrost operation In heating operation freezing of the heat exchanger unit s air cooled coil increases over time restricting the energy transfer to the heat exchan...

Page 27: ...irection adjust button only for double flow multi flow corner ceiling suspended and wall mounted Refer to 12 4 Adjusting the air flow direction on page 27 for details To stop 5 Press the ON OFF button...

Page 28: ...ter diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth 13 1 After sales service and warranty 13 1 1 Warranty period This product includes a warranty card...

Page 29: ...the warranty card 14 1 Error codes Overview In case a malfunction code appears on the indoor unit user interface display contact your installer and inform the malfunction code the unit type and serial...

Page 30: ...s max till this process is finished 14 2 4 Symptom The fan strength does not correspond to the setting The fan speed does not change even if the fan speed adjustment button in pressed During heating o...

Page 31: ...ptom The heat exchanger unit fan does not spin During operation The speed of the fan is controlled in order to optimise product operation 14 2 15 Symptom The display shows 88 This is the case immediat...

Page 32: ...4P408443 1 0000000L 4P408443 1 2015 07 Copyright 2015 Daikin...

Reviews: