background image

13 Maintenance and service

Installation and operation manual

28

RKXYQ5T7Y1B

VRV IV compressor unit for indoor installation

4P408443-1 – 2015.07

2

In case of VRV DX indoor units combined with an air
handling unit

a

Heat exchanger unit

b

Compressor unit

c

Refrigerant piping

d

User interface (dedicated depending on indoor unit type)

VRV DX

VRV direct expansion (DX) indoor unit

EKEXV

Expansion valve kit

AHU

Air handling unit

When  the  system  is  installed  as  shown  in  the  figure  above,  it  is
necessary to designate one of the user interfaces as the master user
interface.

The  displays  of  slave  user  interfaces  show 

  (change-over

under  centralised  control)  and  slave  user  interfaces  automatically
follow the operation mode directed by the master user interface.

Only the master user interface can select heating or cooling mode.

12.5.2

To designate the master user interface
(VRV DX)

1

Press the operation mode selector button of the current master
user interface for 4 seconds. In case this procedure was not yet
performed,  the  procedure  can  be  executed  on  the  first  user
interface operated.

Result: 

The  display  showing 

  (change-over  under

centralised control) of all slave user interfaces connected to the
same compressor unit flashes.

2

Press  the  operation  mode  selector  button  of  the  controller  that
you wish to designate as the master user interface.

Result: 

Designation  is  completed.  This  user  interface  is

designated  as  the  master  user  interface  and  the  display
showing 

  (change-over  under  centralised  control)

vanishes.  The  displays  of  other  user  interfaces  show 
(change-over under centralised control).

13

Maintenance and service

NOTICE

Never  inspect  or  service  the  unit  by  yourself.  Ask  a
qualified service person to perform this work.

WARNING

Never replace a fuse with a fuse of a wrong ampere ratings
or  other  wires  when  a  fuse  blows  out.  Use  of  wire  or
copper wire may cause the unit to break down or cause a
fire.

CAUTION

Do not insert fingers, rods or other objects into the air inlet
or  outlet.  Do  not  remove  the  fan  guard.  When  the  fan  is
rotating at high speed, it will cause injury.

CAUTION

After  a  long  use,  check  the  unit  stand  and  fitting  for
damage. If damaged, the unit may fall and result in injury.

NOTICE

Do  not  wipe  the  controller  operation  panel  with  benzine,
thinner,  chemical  dust  cloth,  etc.  The  panel  may  get
discoloured  or  the  coating  peeled  off.  If  it  is  heavily  dirty,
soak  a  cloth  in  water-diluted  neutral  detergent,  squeeze  it
well  and  wipe  the  panel  clean.  Wipe  it  with  another  dry
cloth.

13.1

After-sales service and warranty

13.1.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If  repairs  to  the  air  conditioner  are  necessary  within  the  warranty

period, contact your dealer and keep the warranty card at hand.

13.1.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend  to  enter  into  a  maintenance  and  inspection  contract  on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep  your  air  conditioner  in  operation  as  long  as  possible.  Contact
your dealer for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the air conditioner.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do not modify, disassemble, remove, reinstall or repair

the unit yourself as incorrect dismantling or installation
may  cause  an  electric  shock  or  fire.  Contact  your
dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustible  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  Always  have  qualified  service
personnel  confirm  that  the  point  of  leakage  has  been
repaired or corrected before resuming operation.

14

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system must be repaired by a qualified service person:

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does not properly work.

Turn off the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does not work
well.

Turn off the power.

Summary of Contents for RKXYQ5T7Y1B

Page 1: ...Installation and operation manual VRV IV compressor unit for indoor installation English Installation and operation manual VRV IV compressor unit for indoor installation RKXYQ5T7Y1B...

Page 2: ...e dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti at...

Page 3: ...components 15 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 and default situation 16 6 1 6 To use mode 2 17 6 1 7 Mode 1 and default situation Monitoring settings 17 6 1 8 Mode 2 Field settings...

Page 4: ...unit Heat exchanger unit installation manual Installation instructions Format Paper in the accessory bag of the heat exchanger unit Installer and user reference guide Preparation of the installation...

Page 5: ...stallation site 4 1 1 Installation site requirements of the compressor unit Service space Mind the following requirements 10 a 10 10 500 10 mm 3D098835 1 b a Top view b Front view NOTICE This is a cla...

Page 6: ...HP Piping outer diameter size mm Gas pipe Liquid pipe Standard Size up 5 15 9 19 1 9 5 C Piping between refrigerant branch kits Use the following diameters Indoor unit capacity index Piping outer diam...

Page 7: ...tted to the building use a vibration proof rubber field supply You can install the compressor unit directly on the floor or on a structure On the floor You do NOT have to fix the unit with anchor bolt...

Page 8: ...mm 22 5 27 5 5 3 2 To remove the pinched pipes WARNING Any gas or oil remaining inside the stop valve may blow off the pinched piping Failure to observe the instructions in procedure below properly ma...

Page 9: ...hole b Hit on the knockout hole and remove it c Remove the burrs d Paint the edges and areas around the edges using repair paint to prevent rusting NOTICE Precautions when making knockout holes Avoid...

Page 10: ...ping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been factory tested for leaks On...

Page 11: ...orrosive effect between the brass flare nut and the copper flare 5 4 5 To perform vacuum drying To remove all moisture from the system proceed as follows 1 Evacuate the system for at least 2 hours to...

Page 12: ...ill take longer then Stage 2 Manual charging Only necessary if the determined additional refrigerant amount is not reached yet by pre charging Stage 1 Pre charging Summary Pre charging Refrigerant bot...

Page 13: ...efrigerant on page 13 and solve the malfunction accordingly Resetting the malfunction can be done by pushing BS3 You can restart the Charging instructions Aborting the manual refrigerant charge is pos...

Page 14: ...cal wiring on the compressor unit NOTICE Follow the wiring diagram delivered with the unit located on the switch box cover Make sure the electrical wiring does NOT obstruct proper reattachment of the...

Page 15: ...C configurator You can also make field settings through a personal computer interface for this option EKPCCAB is required The installer can prepare the configuration off site on PC and afterwards uplo...

Page 16: ...re operation in order to have power running to the crankcase heater and to protect the compressor Turn on the power supply of the compressor unit heat exchanger unit and all indoor units When the comm...

Page 17: ...set in mode 2 There are two methods to activate low noise operation of the compressor unit and heat exchanger unit The first method is to enable an automatic low noise operation during night time by f...

Page 18: ...settings In mode 2 you can make field settings to configure the system The LEDs give a binary representation of the setting value number Setting binary Value Description 2 8 Te target temperature dur...

Page 19: ...ne the level of operation Depending on the chosen level the noise level will be lowered The start and stop moments for this function are defined under setting 2 26 and 2 27 default Deactivated Level 1...

Page 20: ...t exchanger unit while performing a test operation is dangerous NOTICE Be sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the c...

Page 21: ...erform a test run 7 3 1 About test run The procedure below describes the test operation of the complete system This operation checks and judges following items Check of wrong wiring communication chec...

Page 22: ...splayed on the user interface of the indoor unit 8 1 1 Error codes Overview Main code Cause Solution Heat exchanger fan malfunction Drain pump feedback contact is open In the heat exchanger unit Check...

Page 23: ...anger unit capacity setting malfunction Check the type of heat exchanger unit If necessary replace the heat exchanger unit Insufficient supply voltage Check if the supply voltage is supplied properly...

Page 24: ...vice port refrigerant charge f Filter 5 g Subcool heat exchanger h Pressure regulating valve i Capillary tube j Accumulator k Compressor accumulator l Heat exchanger M1C Compressor M1F M2F Fan motor R...

Page 25: ...g cooling applications NOTICE Do not use the air conditioner for other purposes In order to avoid any quality deterioration do not use the unit for cooling precision instruments food plants animals or...

Page 26: ...om dropping or cold air from blowing Defrost operation In heating operation freezing of the heat exchanger unit s air cooled coil increases over time restricting the energy transfer to the heat exchan...

Page 27: ...irection adjust button only for double flow multi flow corner ceiling suspended and wall mounted Refer to 12 4 Adjusting the air flow direction on page 27 for details To stop 5 Press the ON OFF button...

Page 28: ...ter diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth 13 1 After sales service and warranty 13 1 1 Warranty period This product includes a warranty card...

Page 29: ...the warranty card 14 1 Error codes Overview In case a malfunction code appears on the indoor unit user interface display contact your installer and inform the malfunction code the unit type and serial...

Page 30: ...s max till this process is finished 14 2 4 Symptom The fan strength does not correspond to the setting The fan speed does not change even if the fan speed adjustment button in pressed During heating o...

Page 31: ...ptom The heat exchanger unit fan does not spin During operation The speed of the fan is controlled in order to optimise product operation 14 2 15 Symptom The display shows 88 This is the case immediat...

Page 32: ...4P408443 1 0000000L 4P408443 1 2015 07 Copyright 2015 Daikin...

Reviews: