IM 926-3 • ROOFPAK APPLIED SYSTEMS 16 www.DaikinApplied.com
Introduction
FanTrol
The FanTrol, provided on all units, is a method of head
pressure control that automatically cycles the condenser
fans in response to ambient air temperature. This feature
maintains head pressure and allows the unit to run at low
ambient air temperatures.
RPS/RDT and RCS units have two independent refrigerant
circuits with one to four condenser fans being controlled
independently by the ambient air temperature of each circuit.
Table 4: R-22 FanTrol Setpoints in °F with MicroTech III Controls
RPS, RCS,
RDT, RPR
Degrees Farenheit
B05
B06
B07
B08
Setpoint
Differential
Setpoint
Differential
Setpoint
Differential
Setpoint
Differential
015 to 020C
0
5
60
5
—
—
—
—
025 to 030C
0
5
65
5
—
—
—
—
036
0
5
70
5
—
—
—
—
045 to 045C
0
5
65
5
—
—
—
—
050
0
5
60
5
—
—
—
—
060
0
5
25
5
70
5
—
—
070
0
5
40
5
70
5
—
—
075 to 090C
0
5
65
5
75
5
0
5
105
0
5
0
5
58
5
70
5
Table 5: R-407C FanTrol Setpoints in °F with MicroTech III Controls
RPS, RCS, RDT
Degrees Farenheit
B05
B06
B07
B08
Setpoint
Differential
Setpoint
Differential
Setpoint
Differential
Setpoint
Differential
015
0
5
60
5
—
—
—
—
018 to 020C
0
5
0
5
—
—
—
—
025 to 036C
0
5
65
5
—
—
—
—
040
0
5
60
6
—
—
—
—
045
0
5
55
5
—
—
—
—
050
0
5
50
5
—
—
—
—
060
0
5
15
5
70
5
—
—
070
0
5
30
5
70
5
—
—
075
0
5
65
5
75
5
0
5
080 to 090C
0
5
65
5
75
5
0
5
105
0
5
0
5
52
5
70
5