Troubleshooting by Remote Controller
SiBE341001
119
Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
A
NO
Remove the foreign substances.
Check if any foreign
substances around
the fan.
Check electric motor (electric motor) corresponding to
malfunction code “E7” in the monitor mode of outdoor unit
PCB. (Refer to P.106~P.107 for how to check)
Check in the monitor mode
Cut the power supply OFF and wait for 10 minutes.
{
Fan motor: relay connector or X1A, X2A of compressor
inverter PCB.
Check the connection status of the connectors
Check if any
connector is
disconnected.
{
Fan motor: Both power supply wire and signal wire are all
white.
Check the color of relay connectors
Relay
connectors have
any connection
error.
Insert the connector.
Correct the connection of the relay
connectors.
YES
YES
NO
YES
NO