Troubleshooting by Remote Controller
SiBE341001
127
Troubleshooting
2.15
“
F9
”
Outdoor Unit : Malfunction of BS Unit Electronic
Expansion Valve
Remote
Controller
Display
F9
Applicable
Models
BSVQ100-250PV1
RQCE-PY1
Method of
Malfunction
Detection
This malfunction is detected by whether or not all coils of the electronic expansion valve have
continuity.
Malfunction
Decision
Conditions
When the power supply turns ON, there is no currents pass through the common (COM[+]).
Supposed
Causes
Connector disconnected from the electronic expansion valve
Faulty of the electronic expansion valve coil
Faulty PCB of the BS unit