SiBE341001
Troubleshooting by Remote Controller
Troubleshooting
132
2.18
“
J3
,
J4
,
J5
,
J6
,
J7
,
J8
,
J9
”
Outdoor Unit: Malfunction of
Outdoor unit Thermistor
Remote
Controller
Display
J3
,
J4
,
J5
,
J6
,
J7
,
J8
,
J9
Applicable
Models
RQYQ-PY1
RQEQ-PY1
Method of
Malfunction
Detection
Malfunction is detected from the temperature by each thermistor.
Malfunction
Decision
Conditions
When a thermistor disconnection or short circuit occurs during operation.
Supposed
Causes
Defect of connection of thermistor
Defect of thermistor
Defect of outdoor unit PCB