SiBE341001
Troubleshooting by Remote Controller
Troubleshooting
138
2.21
“
L1
”
Outdoor Unit: Malfunction of Inverter PCB
Remote
Controller
Display
L1
Applicable
Models
RQYQ-PY1
RQEQ-PY1
Method of
Malfunction
Detection
Malfunction is detected based on the current value during waveform output before starting
compressor.
Malfunction is detected based on the value from current sensor during synchronous
operation when starting the unit.
Malfunction
Decision
Conditions
Overcurrent (OCP) flows during waveform output.
Malfunction of current sensor during synchronous operation.
IPM failure.
Supposed
Causes
Inverter PCB (A3P)
z
IPM failure
z
Current sensor failure
z
Drive circuit failure