SiBE341001
Troubleshooting by Remote Controller
Troubleshooting
140
2.22
“
L4
”
Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise
Remote
Controller
Display
L4
Applicable
Models
RQYQ-PY1
RQEQ-PY1
Method of
Malfunction
Detection
Radiation of compressor inverter PCB.
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases above 87°C.
Supposed
Causes
Actuation of fin thermal (Actuates above 87°C)
Defect of inverter PCB
Defect of fin thermistor