P1
”
Outdoor Unit: Inverter Over-Ripple Protection
Remote
Controller
Display
P1
Applicable
Models
RQYQ-PY1
RQEQ-PY1
Method of
Malfunction
Detection
Imbalance in supply voltage is detected in PCB.
Malfunction
Decision
Conditions
When the amplitude of the ripple exceeding 6V is detected.
Malfunction is not decided while the unit operation is continued.
“
P1
” will be displayed by pressing the inspection button.
Supposed
Causes
Open phase
Voltage imbalance between phases
Defect of main circuit capacitor
Defect of inverter PCB
Defect of K2M relay in inverter PCB
Improper main circuit wiring