Troubleshooting by Remote Controller
SiBE341001
155
Troubleshooting
Troubleshooting
YES
Replace the outdoor
unit main PCB.
YES
YES
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace it with the
correct compressor
inverter PCB.
Is the
type of the compressor
inverter PCB (A3P)
correct?
NO
Replace it with the
correct fan inverter
PCB.
Is the
type of the fan inverter
PCB (A4P) correct?
NO
Rectify the connection
wiring.
Does the
preparation indication
lamp (H2P) on the main
PCB turn
OFF?
NO
Set the dip switches
correctly.
(After setting: Reset the
power supply)
Is the
setting of dip switches
when replace the main
PCB correct?