Troubleshooting by Remote Controller
Troubleshooting
176
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace the main PCB of the
outdoor unit.
• With individual systems, replace
the control PCB (A1P).
• With multi systems, replace the
main PCB (A1P).
Confirmation of malfunction 3 Confirmation of malfunction 4
YES
NO
YES
NO
Diagnosis Flow 1
Confirmation of malfunction 3 Confirmation of malfunction 4
Diagnosis Flow 2
The number of indoor
units connected to the
same refrigerant circuit
system should not be
more than 64 units.
The number of indoor units
exceeds the standard. Check the
connection to correct.
Check if the refrigerant
type of the outdoor unit
corresponds to that of the
indoor unit.
Replace the main PCB of the
outdoor unit.
• With individual systems, replace
the control PCB (A1P).
• With multi systems, replace the
main PCB (A1P).
Match the refrigerant types of the
outdoor unit and the indoor unit.
Summary of Contents for RQYQ140-180PY1
Page 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Page 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Page 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Page 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Page 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Page 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Page 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...