Refrigerant Circuit
SiBE341001
21
Refrigerant Circuit
1.2
BS Unit
• BSVQ100 ~ 250PV1
4D057985B
No.
Name
Symbol
Function
1
Electronic expansion valve (EVSC)
Y1E
In simultaneous cooling and heating operation, it is used to subcooling
liquid refrigerants when an indoor unit downstream of this BS unit is in
heating operation.
2
Electronic expansion valve (EVHS)
Y2E
Opens while in heating operation or all indoor units are in cooling
operation.
3
Electronic expansion valve (EVLS)
Y3E
Opens while in cooling operation.
4
Electronic expansion valve (EVH)
Y4E
Opens while in heating operation or all indoor units are in cooling
operation.
5
Electronic expansion valve (EVL)
Y5E
Opens while in cooling operation.
6
Capillary tube
—
Used to bypass high pressure gas to low pressure side to protect
“Refrigerant accumulation” in high and low pressure gas pipes.
7
Double pipe heat exchanger
—
In simultaneous cooling and heating operation, it is used to subcooling
liquid refrigerants when an indoor unit downstream of this BS unit is in
heating operation.
(1)
(7)
(6)
(2)
(4)
(3)
(5)
Summary of Contents for RQYQ140-180PY1
Page 216: ...Piping Diagrams SiBE341001 207 Appendix 1 2 BS Unit BSVQ100 160 250PV1 4D057985B...
Page 217: ...SiBE341001 Piping Diagrams Appendix 208 BSV4Q100PV1 3D064148...
Page 218: ...Piping Diagrams SiBE341001 209 Appendix BSV6Q100PV1 3D064149...
Page 220: ...Wiring Diagrams for Reference SiBE341001 211 Appendix 2 2 BS Unit BSVQ100 160 250PV1 3D055928C...
Page 221: ...SiBE341001 Wiring Diagrams for Reference Appendix 212 BSV4Q100PV1 3D063928B...
Page 222: ...Wiring Diagrams for Reference SiBE341001 213 Appendix BSV6Q100PV1 3D063929B...
Page 223: ...SiBE341001 Option List Appendix 214 3 Option List 3 1 Option Lists Outdoor Unit 3D066354...